High Elevation; Gas Line Installation; Gas Pipe Pressure Testing; I.t. Valve Description - Regency L390E Owner's Manual

Gas insert
Hide thumbs Also See for L390E:
Table of Contents

Advertisement

L390E-2 NG / HZI390E-2 NG
SYSTEM DATA
Min. Supply Pressure 5" WC (1.25 kpa)
Manifold Pressure
3.5" WC (0.87 kpa)
Orifi ce Size
#35 DMS
Maximum Input
31,000 Btu/h
(9.09 kW)
L390E-2 LP / HZI390E-2 LP
SYSTEM DATA
Min. Supply Pressure
11" WC (2.73 kpa)
Manifold Pressure
10" WC (2.49 kpa)
Orifi ce Size
#53 DMS
Maximum Input
31,000 Btu/h
(9.09 kW)

HIGH ELEVATION

This unit is approved for altitude 0 to 4500 ft. (CAN1
2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and fl ex connectors are
usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.
L390E-2 / HZI390E-2 Direct Vent Gas Insert
Burner
Flame Sensor
Pilot
Note: If you have an incorrect fl ame pattern,
contact your Regency
instructions.
Incorrect fl ame pattern will have small, probably
yellow fl ames, not coming into proper contact
with the rear burner or fl ame sensor.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa). Disconnect
piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" fl at screwdriver.
Note: Screw should be snug, but do not over
tighten.
885 S.I.T. VALVE
1) 6 Stage fl ame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
Ignitor
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
®
dealer for further
3
4
5
6
INSTALLATION
DESCRIPTION
2
1
7
19