5. Maintenance and insection
Do not short-circuit the battery with a metal object.
● Doing so may result in burn injury or fire.
● Even in a dead battery, there is some current remaining.
Do not toss a battery into a fire. Do not try to break a battery.
● The battery may explode or dilute sulfuric acid may leak.
Do not use any batteries unless otherwise specified.
● Doing so may lead to a fire.
● Battery pack product models: BP150XR (for BN100XR, BN150XR), BP240XR (for BN240XR,
MB240XR)
Do not use a new battery and an old battery at the same time
(when adding BN240XR battery).
● Rapid deterioration of battery may occur, and dilute sulfuric acid may leak.
Do not drop the battery and make sure that it does not receive any strong
impact.
● Dilute sulfuric acid may leak.
Do not replace the battery in a place near flammable gas.
● A spark may occur when connecting the battery, and lead to a fire.
Replace a battery on a structurally sound base.
● Hold the battery securely with both hands to avoid dropping.
● Failure to do so may result in injury due to the battery falling, burns, or injury.
Do not disassemble or modify the battery.
● Doing so may cause a leakage of dilute sulfuric acid, which may cause blindness and burns.
The UPS uses a lead acid battery.
The lead acid battery is recyclable.
● For information about recycling and disposing of unneeded batteries, contact the Electronic
Systems & Equipments repair center.
1. Changing the battery for BN100XR/BN150XR
● Replaceable battery pack
Cautions
Notes
Model name: BP150XR
A Use a screwdriver to pry off the square plate on the
left with the OMRON logo printed on it.
B Remove the two screws.
C Pull the left side of the plastic panel toward you.