TECHNICAL FEATURES AND DIMENSIONS 1. 1 INTRODUCTION flue length of 3 m [118 in]. The combined flue and air duct can exit the boiler from either The Sime “SUPERIOR Ci” is a range of wall mounted cast iron side or from the rear of the appliance. boilers.
Page 4
GENERAL DATA TABLE 3a - Nominal boiler ratings (2 minutes after lighting) for Superior 40 Ci MODE OUTPUT INPUT (N.C.V.) INPUT (G.C.V.) BURNER PRESSURE Btu/h Btu/h mbar inwg CENTRAL HEATING RANGE 30,000 10.0 11. 1 37,800 9. 1 31,000 10.3 11.4...
Page 5
TABLE 4 - General specifications 40 Ci 50 Ci 60 Ci 80 Ci Burner Injector ø mm 3.25 3.25 3.55 4. 1 0 Max. gas consumpt. 1,38 1,69 2,05 2,75 System Press 0. 1 2 0. 1 2 0. 1 2 0.
GENERAL REQUIREMENTS FOR INSTALLATION 2. 1 STATUTORY REQUIREMENTS – A compartment used to enclose the appliance MUST be designed and constructed specifically for this purpose. An GAS SAFETY [INSTALLATION AND USE REGULATIONS [as existing cupboard, or compartment, may be used provided amended].
Page 7
VENTILATION REQUIREMENTS The domestic hot water cylinder must be of the indirect type with a separate feed and vent pipes. Single feed cylinders Detailed recommendations for air supply are given in must not be used. B55440: 2. The pump, including isolation valves, should be fitted in the The following notes are for general guidance: heating flow pipe from the appliance.
Page 8
ALTERNATIVE METHODS OF FILLING A SEALED SYSTEM Fig. 4 priate to one of these methods. The system pressure must a range of 0 to 5 bar, or similar, is suitable. not be less than the static head of the system. A suitable expansion vessel must be fitted to the system.
Page 9
TYPICAL SYSTEM DESIGN, FULLY PUMPED, OPEN VENTED. Fig. 6 2.8.6 Combined pumped C.H. & Gravity D.H.W. systems ter and be connected to each of the 22 mm connections on the flow and return manifolds. A gravity system requires a When this option of system is chosen: minimum circulating head of 1 m assuming there is no hori- The gravity hot water pipes to the indirect hot water cylinder zontal pipe run.
INSTALLING THE BOILER Appliance package: – Boiler (appliance + mounting frame) – Installation, servicing and User instructions – Wall template MOUNTING – Fixing screws with wall plugs and washers BRACKET – 2x28 mm olives part no. 6100204 – 2x22 mm olives part no. 6100203 3.
Page 11
Horizontal coaxial duct lenght (Z fig. 10-13) from 380 to 580 mm from 580 to 1500 mm from 1500 to 3000 mm Standard diaphragm Optional diaphragm Diaphragm Superior 40 Ci Ø 79 Ø 84 (Code 6028622) Superior 50 Ci Ø 81 Ø...
Page 12
– Remove the six fixing screws securing the sealed chamber GAS CONNECTIONS front panel then remove the panel. – Place the gasket (G) under the flange of the elbow and fit The gas service cock is located at the bottom right hand side the elbow onto the top of the appliance, taking care to of the appliance.
Page 13
Fully pumped or combined pumped and gravity operation installed within a combined pumped and gravity system, the The appliance is supplied ready for installation within a fully switch on the rear of the control box should be set to gravity pumped heating/hot water system.
Page 14
FULLY PUMPED SYSTEM USING TWO ZONE VALVES Fig. 18 FULLY PUMPED SYSTEM USING MID POSITION ZONE VALVE Fig. 19 Supplied By www.heating spares.co Tel. 0161 620 6677...
COMMISSIONING AND TESTING SIME SUPPORT THE BENCHMARK INITIATIVE to maximum and a final check completed. – Turn off the system and drain for the final time. All relevant sections of the logbook must be filled in at the – Refill and vent the system completely.
ROUTINE SERVICING INSTRUCTIONS To ensure continued efficient operation of the appliance, it is – Unscrew the 2 screws securing the combustion chamber recommended that it is checked and serviced as necessary front panel and remove the panel, taking care not to dama- at regular intervals.
FAULT FINDING When any service or replacement of electrical components necting and checking each component] is required to trace which has required the breaking and re-making of electrical the faulty component. connections has taken place, the following tests must be repeated: It is possible that a fault could occur as a result of local bur- –...
Page 18
FAULT FINDING 3) Turn ON external gas and electricity supplies. 4) Ensure there is 230 V at the permanent live “PHASE” on Before proceeding through this fault finding guide: the installation terminal block. 1) ensure all connections to the electronic circuit board 5) Ensure there is 230 V at the switched live “HEAT and the 12 way connector to the ignition device are cor- DEMAND”...
REPLACEMENT OF PARTS Before commencing any service operation, ISOLATE the CONTROL TEMPERATURE SENSOR mains electrical supply, and TURN OFF the gas supply at the main service cock. It is the law that any service work must be – Remove the casing by unscrewing the retaining screws at carried out by registered person [C.O.R.G.I.].
Page 21
box, taking note of their respective position. screws at bottom rear of the appliance and pulling the – Slide the burner forwards and at the same time feed the panel forwards, lifting it off the two pins at the top two two wires through the grommet in the sealed chamber.