3 Piping work and
refrigerant charge
• Dimensions of the flared pipe
Units: mm (inch)
Nominal
External
A
diameter
diameter
(1/4)
6.35
(3/8)
9.53
(1/2)
12.7
(5/8)
15.88
• Thickness of the copper pipes
Units: mm (inch)
Nominal
External
Thickness
diameter
diameter
(1/4)
6.35
(3/8)
9.53
(1/2)
12.7
(5/8)
15.88
• Dimensions of the flare nut
Units: mm (inch)
Nominal
External
diameter
diameter
(1/4)
6.35
(3/8)
9.53
(1/2)
12.7
(5/8)
15.88
• Flare nuts tightening torque
Always use two wrenches or fix spanners when tightening the Flare Nuts on the refrigerent pipes.
If any failure occurs during this process the result could be pipe damage or refrigerant leak.
Unit: N.m
Pipe size
Tightening torque
Ø 6.35 mm
20
Ø 9.53 mm
40
Ø 12.7 mm
60
Ø 15.88 mm
80
65
SMGB0070 rev.1 - 08/2011
Ø +0/-0.4
9.1
13.2
16.6
19.7
0.80
0.80
0.80
1.00
B
17
22
26
29
3