11 Servicing
18 Remove plate heat exchanger with water and refrigerant
pipes and expansion valve.
19 Install new one by performing the procedures above in
reverse way.
N O T E
• Be careful do not lose the gaskets.
• Check the gaskets, if it is defective, replace by a
new ones.
In case on remove only the heat exchanger.
1 Remove service cover.
2 Remover electrical box cover.
3 Turn electrical box by removing screws.
4 Remove manometer by perform procedure
nometer.
5 Remove LCD controller by perform procedure
LCD
controller.
6 Remove LCD control control support by unscrew nuts.
7 Remove Refrigerant liquid thermistor (THM
by perform procedure
Replace
8 Remove brazing from the four places (refrigerant side
and water side).
9 Unscrew the two nuts holding the plate heat exchanger.
10 Remove plate heat exchanger .
11 Install new one by performing the procedures above in
reverse way.
325
SMGB0070 rev. 1 - 08/2011
Replace ma-
Replace
) from pipe
L
thermistors.
Brazing
Brazing
11
Screw nuts