2 Unit installation
-
RAS-(3-6)H(V)RNME-AF
Single Installation
100 mm or more of the side space is acceptable on the service cover
side. Dimensions in ( ) shows numbers especially for IVX 4-10 HP. 150
or more (200 or more) of the back space is acceptable when the right 
and left sides are open.
Be sure to use the fan direction guide. Leave open both right and
left sides.
Single Installation
100 mm or more of the side space is acceptable on the service
cover side.
Dimensions in ( ) shows numbers especially for IVX 4-10 HP.
Be sure to use the fan direction guide.
Leave open both right and left sides.
20
SMGB0070 rev. 1 - 08/2011
Blocked in Inlet Side
Upper Side Open
Multiple Installation (Two units or more)
Allow 100 mm of space between units. Leave open both right and left
sides.
Dimensions in ( ) shows numbers especially for IVX 4-10 HP.
Be sure to use the fan direction guide. Allow 100 mm of space
between units. Leave open both right and left sides.
When subject to direct sunlight on the back wall ensure the length 
marked with . be 500 or greater.
Upper Side Blocked
Multiple Installation (Two units or more)
Allow 100 mm of space between units. Leave open both right and
left sides.
Dimensions in ( ) shows numbers especially for IVX 4-10 HP.
Be sure to use the fan direction guide. Allow 100 mm of space
between units. Leave open both right and left sides.
Serial installation allowed up to two units.