Appendix C: Power Boosters and Load Interfaces

This "load-side" equipment installs on the zone wiring between
the Control Unit and the lighting load.
The NGRX-PB increases a Control Unit's zone load capacity
for Incandescent/Halogen (Tungsten), Magnetic Low Voltage,
and Neon/cold Cathode load types.
The ELVI-1000 enables a zone of the Control Unit to control
electronic low-voltage loads.
The FDBI-16A-120 enables a zone on the Control Unit to
operate fluorescent loads outfitted with Lutron's Hi-Lume or
Eco-10 phase-controlled dimming ballasts.
Unit
120V
220-240V (AU)
PB
1920W/VA
2400W/VA
FDBI
1920W/VA
2400W/VA
ELVI
1000W/VA
1200W/VA
* 1840W/VA surface mount, 1200W/VA flush mount.
Wiring detail
PB OR ELVI (REAR VIEW)
EACH TERMINAL CAN
ACCEPT UP TO 2 #12 AWG
2
(2.5 mm
) WIRES
ZONE
NEUTRAL
DIMMED HOT/LIVE OUT
HOT/LIVE IN
FDBI (REAR VIEW)
EACH TERMINAL CAN
ACCEPT UP TO 2 #12 AWG
2
(2.5 mm
) WIRES
ZONE
NEUTRAL
SWITCHED HOT/LIVE OUT
NEUTRAL
DIMMED
HOT/LIVE OUT
* Can be on the same or different phases.
CAUTION! Test load for short circuits.
Turn power off.
PB/ELVI: Connect standard switch between
hot/live lead and the load wire to test circuit.
FDBI: Connect standard switch between
hot/live lead and both the dimmed hot/live
and switched hot/live leads of the ballast.
Turn power on and check for short or open
circuits.
230V (CE)*
1840W/VA
2400W/VA
Wiring instructions
1200W/VA
1. Turn off power to the Control Unit and the feed to the PB, ELVI, or FDBI!
2. Mount 2-gang wallbox: 3 1/2 in. (87.5 mm) deep recommended, 2 3/4 in. (68.75 mm)
deep minimum. When mounting several units in a vertical layout (one underneath the
other), allow at least 4 1/2 in. (11 cm) between units.
3. Strip 1/2 in. (12 mm) insulation from #12 (2.5 mm
connect as shown. Please see the Instruction Sheet supplied with the unit for more
detailed wiring diagrams.
CONTROL UNIT
FROM
DISTRIBUTION
PANEL
:
NEUTRAL
HOT/LIVE IN*
FROM
DISTRIBUTION
PANEL:
LOAD
NEUTRAL
HOT/LIVE IN*
CONTROL UNIT
FROM
DISTRIBUTION
PANEL
:
NEUTRAL
HOT/LIVE IN*
FROM
DISTRIBUTION
HI-LUME OR ECO-10 BALLAST
PANEL:
TO LAMPS
NEUTRAL
HOT/LIVE IN*
Mounting
IMPORTANT WIRING NOTES!
Connect ZONE OUT only to Lutron Hi-Lume or Eco-10
Electronic Dimming Ballasts. Do not use this connection
with any other fluorescent ballast or transformer.
Page 11
HOT/LIVE
SWITCH
LOAD
PB/ELVI
SWITCH
HOT/LIVE
ORANGE
BALLAST
BLACK/BROWN
FDBI
2
) 75 °C copper (CU) AWG wires and