Finishing; Mantel Projections; Facing Material - Heat & Glo 8000CF-OAK-IPI Owner's Manual

Installation and operation
Hide thumbs Also See for 8000CF-OAK-IPI:
Table of Contents

Advertisement

11
11

Finishing

A. Mantel Projections
Figure 11.1 shows the minimum vertical and corresponding
maximum horizontal dimensions of mantels or other
combustible projections above the top front edge of the
appliance.
Note: All
measurements
in inches.
10-1/2
6-3/4
3
7-3/4
MEASUREMENTS FROM
TOP EDGE OF HOOD
Figure 11.1Clearances to Mantels or other Combustibles above
Appliance
TOP VIEW
3 in.
MIN.
Note: Clearance from opening
to perpendicular wall.
Figure 11.2 Mantel Leg or Wall Projections
(Acceptable on both sides of opening).
B. Facing Material
WARNING
Fire Risk
Explosion Risk
• Facing and/or fi nishing materials must never
overhang into the glass opening.
• Overhanging materials may ignite.
• May interfere with proper operation of glass
assembly.
18
14-1/4
12-1/4
11-1/8
10
8-7/8
1 in.
MIN.
3 ft.
MAX.
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. o • 12/07
FINISH WALL MATERIAL MAY BE
COMBUSTIBLE - TOP AND SIDES
NON-COMBUSTIBLE
BOARD
0 in.
SEALANT MATERIAL
Figure 11.3 Noncombustible Facing Diagram
WARNING
Risk of Fire
• Non-combustible clearances MUST be
maintained.
• Sheetrock, wood or other combustibles must
NOT be used as sheathing or facing in the
non-combustible zone.
• See Section 11 for proper clearances.
• See Section 1 for combustible/non-combustible
defi nitions.
WARNING
Fire Risk.
Finish all edges and fronts to clearances and
specifi cations listed in manual.
Black metal appliance front may be covered with
noncombustible material only.
Do NOT overlap combustible materials onto appliance
front.
Install combustible materials only up to specified
clearances on top, front and side.
Seal joints between the fi nished wall and appliance top
and sides using only a 300º F minimum sealant.
0 in.
0 in.
35