Schwank STR-JZ Installation & Owner's Manual page 7

Low intensity tube type infra red heater residential garage / workshop
Table of Contents

Advertisement

FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - refer to Table 1 for values
NOTE: A 'PEEL & STICK' SIGN IS SUPPLIED: USE AN INDELIBLE MARKER TO
ENTER VALUES 'H', 'S', 'F', & 'B' ON .
POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.
Suspended at an
angle up to 45°
F
Maximum Stack
Height:
H = T- C
'T' is measured
T
on site,
'C' is in Table 1
FLOOR
TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES*
MODEL
inches (cm)
STR-JZ 60
2.5 (6)
STR-JZ 45
2.75 (7)
*The clearance to combustible materials represents the minimum distance that must be main-
tained between the heater and a nearby surface. The stated clearance to combustibles
represents a surface temperature of 90F° (50C°) above room temperature. .
NOTE that in the above table the clearances are measured from the reflector.
It is the installer's responsibility to ensure that building materials with a low heat
tolerance which may degrade at lower temperatures are protected to prevent
degradation.
D
B
C
H
SUSPENDED AT AN ANGLE
UP TO 45 DEGREES
D
B
inches (cm)
inches (cm)
1 (2.5)
17 (43)
1 (2.5)
24 (61)
See next page for details.
A
S
H
FLOOR
F
C
inches (cm)
inches (cm)
34 (86)
1.5 (4)
32 (81)
2.25 (6)
7
Suspended
horizontally
Maximum Stack
Height:
C
H = T- C
T
'T' is measured
on site,
'C' is in Table 1
SUSPENDED
HORIZONTALLY
A
S
inches (cm)
5.5 (14)
7 (18)
S
C
inches (cm)
34 (86)
32 (81)
STR-JZ I&OManual
IM090831
RD: AUG 2009
RL: 09A - BA