4 Installer Settings

The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer
Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped. These
settings are indicated below with comments. More detail on each setting follows this table.
1. Touch and hold down the SYSTEM and CONFIG TouchPads
2. Release both buttons and the first installer setting will be displayed.
3. Change settings as required using the UP or DOWN portion of the SpeedBar
4. Touch NEXT or BACK to move to the next or previous setting, touch RETURN to exit.
NOTE: Shaded areas below do not apply to the 5310.
No. Installer Setting
(
Notes follow this table)
1 Residential or
or Commercial Profile
2 Programming Mode
[note 1]
3 Clock Format
4 Temperature Scale
5 Auto Changeover
6 System Type
7 1st Stage Differential
8 2nd Stage Differential
[note 2]
9 3rd Stage Differential
[note 2]
10 4th Stage Differential
[note 2]
Installer Guide
Factory
Setting
Default
Options
RES
RES
COMM
7 PROG
7 PROG
52 PROG
NO PROG
12 HR
12 HR
24 HR
F DEG
F DEG
C DEG
oF AUTO
oF AUTO
ON AUTO
11CONV
22CONV
32CONV
11CONV
11HP
22HP
32HP
42HP
0.5 DIF1
0.5, 1.0 or
2.0 DIF1
2.0 DIF2
1.0, 2.0, 3.0,
4.0, 5.0 or
6.0 DIF2
2.0 DIF3
1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°,
4.0, 5.0 or
6.0 DIF3
2.0 DIF4
1.0, 2.0, 3.0,
4.0, 5.0 or
6.0 DIF4
10
for 3 seconds.
.
®
Comments
(More information follows this table)
Select for Residential profile
Select for Commercial profile
Select for 7 day programming mode
Select for 5-2 day programming mode
Select for non-programmable mode
Select for 12 hour clock
Select for 24 hour clock
Select for Fahrenheit display
Select for Celsius display
Disables Auto Changeover mode
Enables Auto Changeover mode
Select for 1H/1C Conventional system
Select for 2H/2C Conventional system
Select for 3H/2C Conventional system
Select for 1H/1C Heat Pump system
Select for 2H/2C Heat Pump system
Select for 3H/2C Heat Pump system
Select for 4H/2C Heat Pump system
Select a 1st stage temperature differential of .5°,
1° or 2° F (.25°, .5° or 2° C)
Select a 2nd stage temperature differential of 1°,
2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C)
3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3°C)
Select a 4th stage temperature differential of 1˚,
2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C)