Braeburn 5310 Installer's Manual page 11

Programmable touchscreen thermostats
Hide thumbs Also See for 5310:
Table of Contents

Advertisement

No. Installer Setting
(
Notes follow this table)
11 1st Stage Fan Control
[note 3]
12 Emergency Heat]
Fan Control [note 4]
13 Reversing Valve
(O/B Terminal) [note 5]
14 Fossil Fuel
Backup Heat [note 4]
15 Compressor Power Outage oF CPOP
Protection
[notes 4, 6]
16 AC Power Interrupt
Warning [note 6]
17 Compressor Short
Cycle Protection
18 Residual Cooling
Fan Delay
19 Circulating Fan Lock
20 Adaptive Recovery
Mode (ARM™)
[note 7]
21 Indoor Remote Sensor
Control* [note 8]
22 Lockout Security Level
23 Auto Changeover
Dead Band [note 9]
24 Compressor Balance
Point [notes 4,
10]
25 Auxiliary Heat Balance
Point [notes 4, 10]
26 Outside Air Intake
(A Terminal) [note 11]
27 Heat Set Point Upper Limit 90LIM
28 Cool Set Point Lower Limit 45LIM
*When a Braeburn
outdoor sensor is connected, the thermostat automatically recognizes it. Press room temperature digits to
®
display outdoor temperature.
NOTE: Additional options such as Service Monitors, Setting the lock code, audible tone, etc. are located in the
User Settings – See User manual for information on setting these options.
Factory
Setting
Default
Options
HG FAN 1
HG FAN 1
HE FAN 1
HE EMER
HE EMER
HG EMER
REVO
REVO
REVB
AE AUX
AE AUX
AG AUX
oF CPOP
on CPOP
AC oF MONR AC oF MONR Disables AC Power Interrupt Warning
AC on MONR Enables AC Power Interrupt Warning
5 CSCP
5, 4, 3, 2 or Select a compressor short cycle protection delay of 5,
0 CSCP
60 FAN
90, 60, 30
or 0 FAN
oF CIRC
oF CIRC
on CIRC
oF REC
oF REC
on REC
I SENS
I SENS
E SENS
A SENS
2 LOCK
2 LOCK
1 LOCK
3 BAND
2, 3, 4 or 5
BAND
NO BALC
NO BALC
15-50 BALC Select a Compressor Balance Point of 15°- 50°F
NO BALA
NO BALA
70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F
OR NONE
OR NONE
OR ECON
OR TOD
90-60 LIM
45-80 LIM
Comments
(More information follows this table)
Select for 1st stage Gas heating
Select for 1st stage Electric heating
Select for Electric Emergency Heat
Select for Gas Emergency Heat
Select for cool active Reversing Valve (O terminal)
Select for heat active Reversing Valve (B terminal)
Select for Electric Auxiliary heat (with compressor)
Select for Gas Auxiliary heat (without compressor)
Disables Power Outage Lockout Delay
Enables Power Outage Lockout Delay
4, 3, 2 or 0 minutes
Select a Residual Cooling Fan Delay of 90, 60,
30 or 0 seconds.
Disables Circulating Fan Lock mode
Enables Circulating Fan Lock mode
Disables Adaptive (early) Recovery mode
Enables Adaptive (early) Recovery mode
Temperature is sensed from thermostat only.
Temperature is sensed from remote sensor only.
Temperature is combined with the thermostat and
t he remote sensor.
If locked – Complete lockout is enabled
If locked – Partial lockout is enabled (SpeedBar
still functional)
Select a Dead Band of 2°, 3°, 4° or 5˚ F
(1°, 2° or 3° C) for Auto Changeover mode.
Disables Balance Points
(-9°-10° C)
Disables Balance Points
(21°- 4° C)
Disables Outside Air Intake option
Enables Outside Air Intake (Economizer Mode)
Enables Outside Air Intake (Time of Day Mode)
Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)
Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)
11
is
®
Installer Guide