Figure 16. Typical Suspension Details for Indoor Installation Only
TURBULATOR INSTALLATION
For ease of installation, the turbulator should be installed in the tube before hanging the system.
Use the following procedure (see Figure 17):
1. Assemble turbulator pieces by "twisting" matching ends
together.
2. Insert a long wire (11 ft. (3.3 m) minimum) down the
length of the tube. Attach the wire to the hole in the tab
on the adapter piece.
Lock tab in place
with vent adapter
Last standard section of
heat exchanger tubing
Figure 17. Turbulator Baffle Assembly Detail
Beam
Clamp
3/16" (5 mm)
or larger
Chain
12" (30 cm)
minimum
S-Hook
To Burner
7 :
S E C T I O N
C O M P O N E N T I N S TA L L AT I O N
Locknut
Anchor
Washer
3. Using the wire, pull the assembled turbulator into the
tube from the opposite end. Pull the turbulator through
until just the tab comes out. Detach the wire.
4. Bend the tab around the tube. When installed, the vent
adapter will lock the tab in place.
Attach a wire to this tab.
Turbulator adapter piece
"Twist Lock"
sections together
Pull turbulator into
tube using long wire
Screw Hook
3/8" (9.5 mm)
minimum
Washer
Turbulator 2.5 ft.
section piece
pg 19