RED L.E.D. LIGHT IS ON
MAIN BURNER LIGHTS
NO
YES
SPARK STOPS WHEN
BURNER LIGHTS
NO
YES
SYSTEM RUNS UNTIL CALL
FOR HEAT ENDS
YES
NO
CALL FOR HEAT ENDS:
SYSTEM SHUTS OFF
NO
YES
TROUBLESHOOTING ENDS
→CHECK FOR 24 VAC ACROSS GAS VALVE, IF NO
VOLTAGE, REPLACE IGNITION CONTROL
→SPARK IGNITER MAY BE OUT OF POSITION
→CHECK ELECTRICAL CONNECTION BETWEEN
IGNITION CONTROL AND GAS VALVE , IF OKAY,
REPLACE GAS VALVE.
NOTE: IF IGNITION CONTROL GOES INTO
LOCKOUT, RESET SYSTEM.
→CHECK CONTINUITY OF SENSOR CABLE AND
GROUND WIRE
→CHECK THAT BURNER FLAME COVERS THE
ELECTRODE / SENSOR
→IF CHECKS ARE OKAY, REPLACE IGNITION
CONTROL
NOTE: IF IGNITION CONTROLS GOES INTO
LOCKOUT, RESET SYSTEM
→CHECK CONTINUITY OF SENSOR CABLE AND
GROUND WIRE
→NOTE: IF GROUND IS POOR OR ERRATIC, SHUT
DOWNS MAY OCCUR OCCASIONALLY EVEN
THOUGH OPERATION IS NORMAL AT THE TIME
OF CHECKOUT
→IF CHECKS ARE OKAY, REPLACE IGNITION
CONTROL
→CHECK FOR PROPER TEMPERATURE
CONTROLLER OPERATIONS
→REMOVE VALVE LEAD AIR IGNITION CONTROL, IF
VALVE CLOSES, RECHECK TEMPERATURE
CONTROLLER AND WIRING, IF NOT, REPLACE
GAS CONTROL OPERATOR