RS--0800-LVD User Guide
2
Slide the Cooling module out of the enclosure (see
Figure 4–5 Removing a Cooling Module (2)
4.7.2.2
Inserting the Module
1
Slide the retaining brackets up or down, depending on the location of the cooling module to be installed,
until they are clear of the sides of the Cooling module.
2
Slide the Cooling module fully into the enclosure. A slight resistance will be felt as the connector pushes
home and the rear face of the tray will be flush with the rear members of the enclosure.
3
Return the retaining brackets to the centre position and tighten the securing screws.

4.7.3 I/O Modules

Please refer to section
4.7.3.1
Removing the Module
Warning
Do not remove the I/O module unless you have a replacement unit ready for insertion. The system
must not be run without all units in place.
1
Loosen the screws securing the retaining bracket and slide the bracket downwards, until it is clear of the
side of the I/O module (see
40
2.7
for full information on installing the various I/O module types.
Figure
4–6).
Figure
4–5).