Do you have a question about the 2208e and is the answer not in the manual?
Questions and answers
George
April 15, 2025
how do I get the output 2 to come on? Recently had to swap out the card, I believe I got all the parameters switched over but the output 2 is not kicking on and I'm getting 3FSH fault. Any advice will be greatly appreciated
1 comments:
Mr. Anderson
April 15, 2025
To enable output 2 on a Eurotherm 2208e after swapping out the card and resolving a 3FSH fault, follow these steps:
1. Ensure the correct I/O module for output 2 is physically installed. 2. Power cycle the controller if not already done. 3. Enter configuration mode on the controller. 4. Navigate to the I/O module setup section. 5. Configure output 2 settings as required (e.g., type, function). 6. Exit configuration mode and save settings.
ALARMS..................1-22 1.11.1 Types of Alarm Used in the 2200...........1-22 1.12 ALARM RELAY OUTPUT ............1-23 1.12.1 SETTING ALARM LEVELS ............1-24 1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT .....1-25 1.12.3 DIAGNOSTIC ALARMS ..............1-26 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03...
Page 4
SELECTING AN ACCESS LEVEL ..........3-3 3.3.2 Returning to Operator Level ..............3-5 EDIT LEVEL ..................3-5 3.4.2 Hiding or revealing a complete list ............3-6 3.4.3 Promoting a parameter................ 3-6 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03...
Page 5
Chapter 6 USER CALIBRATION............6-1 WHAT IS THE PURPOSE OF USER CALIBRATION? ....6-2 USER CALIBRATION ENABLE ............6-3 6.10 SINGLE POINT CALIBRATION ...........6-4 6.11 TWO POINT CALIBRATION............6-5 6.12 CALIBRATION POINTS AND CALIBRATION OFFSETS...6-6 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03...
Page 6
To Configure Low and High Current Trip Alarms......9-10 9.9 TO ATTACH SOFT ALARMS TO A RELAY OUTPUT ....9-11 9.10 THE SCALING FACTOR ............9-12 9.1.7 To adjust the scaling factor ............9-12 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03...
Page 7
This product is covered by one or more of the following US Patents: 5,484,206 and 5,793,754; Additional patents pending. PDSIO is a registered trademark of Eurotherm. INSTANT ACCURACY™, SSRx Load Doctor™ and SSRx Enhanced Load Doctor ™...
Page 8
Contents Installation and Operation Handbook Symbols in Use In This Handbook Useful information Button Operation Caution, (refer to the Functional earth accompanying documents) (ground) terminal 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03...
Page 9
1.10.9 Communications List ...............21 1.10.10 Access List ..................21 1.11 alarms..................22 1.11.1 Types of Alarm Used in the 2200 ............22 1.12 Alarm relay output..............23 1.12.1 SETTING ALARM LEVELS .............24 1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT.......25 1.12.3 DIAGNOSTIC ALARMS..............26 2208e and 2204e Controller...
Setpoint 2 active PDS Remote Setpoint Setpoint rate limit active Manual mode Page Scroll Down Button Button Button Button Figure 1-1 Model 2208e front panel layout 2204e Output 1 Output 2 20.00 Upper readout 20.00 Lower readout Setpoint 2 active Remote Setpoint...
Page 11
Press to decrease a value in the lower readout. Up button Press to increase a value in lower readout. Figure 1.3 Controller buttons and indicators For Valve Positioning, please refer to Appendix D ‘Motorised Valve Control 2208e and 2204e Controller...
Operation Installation and Operation Handbook GETTING STARTED Thank you for selecting the 2208e/2204e controller. This section shows the principle of operation. 1.2.1 Viewing The Process Value and Setpoint Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3...
- - - A A A A Manual/Auto Auto Auto Auto Auto Actual state Keep pressing to return to the Home display or select further parameters (if available) Figure 1.6 Upper readout is parameter name. Lower is value 2208e and 2204e Controller...
Figure 1.7 Press to choose a parameter list The actual list headings may be longer or shorter than indicated above and you can customise this for the operator’s convenience in EDIT level, Chapter 3. 2208e and 2204e Controller...
If, at any time, no key is pressed within 45 seconds, the display will always return to the “HOME” display. A complete description of the parameter lists is given on page 1-14. 2208e and 2204e Controller...
3rd press m m m m - - - - A A A A Manual/Auto to select Auto Auto automatic mode Auto Auto manual mode Keep pressing to return to “HOME” display Figure 1.9 Auto/Manual select 2208e and 2204e Controller...
To change the value (or state) of a parameter press the Raise button or the Lower button The remainder of this chapter provides a complete list of all parameters available. 2208e and 2204e Controller...
SSEL SSEL When setpoint 2 is Press SP 1 SP 1 SP 1 SP 1 selected the SP2 beacon change between SP 1 and illuminates. SP 2 Figure 1-11 To Select Setpoint 1 or 2 1-10 2208e and 2204e Controller...
The program will go into rSEt rSEt rSEt rSEt standby Press to choose dwel The program will dwell for an the action required at the end of unlimited period the dwell time Figure 1-12 Ramp/Dwell Program 2208e and 2204e Controller 1-11...
During Dwell. After return of power the working setpoint will servo to PV, the ramp continues to SP2 followed by full programmed dwell. In effect this causes the program to restart. Use the Hide, Reveal and Promote features to customise the display for a programmer. See Chapter 3. 1-12 2208e and 2204e Controller...
The navigation diagram shows a full list of SP2.L possible parameters. However, some may not appear because they are dependent upon the particular controller variant. SP2.H End.t rset 100.0 Loc.L ProG 100.0 rset Loc.H StAt Figure 1.15a Navigation diagram SPrr 1-14 2208e and 2204e Controller...
Complete lists or individual parameters normally hidden in Operator level. To see all the available parameters you must select Full level. See Chapter 3, Access Levels Only displayed when option selected Figure 1.15b Navigation diagram 2208e and 2204e Controller 1-15...
Auto diSP Configure lower None readout of home AmPS display stat vPoS 9999 Customer ID Additional parameters may appear in the Home display if the ‘promote’ feature has been used (see Edit Level, Chapter 3). 1-16 2208e and 2204e Controller...
Hy.EV 9999 Hysteresis for event alarms. See display Note 1 9999 Loop break time secs Note 1: This parameter has been added from software version 4. Event alarms are configured in the AL Conf List 2208e and 2204e Controller 1-17...
Derivative time seconds 0.00 100.0 Manual reset (appears when ti set to OFF) Auto Auto 9999 Cutback low display Auto Auto 9999 Cutback high display rEL.C 1.00 1.00 0.01 9.99 Relative cool gain (set 1) 1-18 2208e and 2204e Controller...
SPrr Setpoint rate limit Units per minute dwEl Dwell time 0.1 to 999.9 minutes EnD.t rset rset rset End type hoLd Stby dwel ProG rset rset Program control rset Stat Status of program dwel 2208e and 2204e Controller 1-19...
1.10.6 On/Off List OnOf OnOf OnOf OnOf On/off list This set of parameters only appear if On/Off control has been configured hYS.H 9999 Heat hysteresis display hYS.C 9999 Cool hysteresis display HC.db 9999 Heat/Cool dead band display 1-20 2208e and 2204e Controller...
Process Variable (PV) Deviation High Deviation Setpoint (SP) Band Deviation Low Full Scale Low Rate of Change Output State Full scale Deviation Deviation high Deviation band Full scale high Rate of change Time Figure 1-17: Alarm Types 1-22 2208e and 2204e Controller...
See Chapter 5 for further information. Alarm 1 Relay Alarm 2 output Alarm 3 SEnS Input fail Sensor break Any combination of alarms can operate the relay. Typical alarms are shown Figure 1-18: Attaching Alarms to an Output 2208e and 2204e Controller 1-23...
4 4 4 4 -- - - - - to change 5th press Loop break time t t t t to change Press to return to list header Figure 1-19 To Set Alarm Trip Levels 1-24 2208e and 2204e Controller...
If a relay has been attached to the alarm output (see Chapter 7 ‘Alarm Operation’), it will operate when the alarm condition occurs and remain in the operated condition until the alarm is acknowledged AND it is no longer present 2208e and 2204e Controller 1-25...
This error message normally occurs when pre- No I/O module configuring a controller without installing any of the Modules are configured but not fitted required I/O modules Figure 1.20a Diagnostic alarms - continued on the next page 1-26 2208e and 2204e Controller...
Page 35
Acknowledge by pressing ‘page’ button error alarm occurs and ‘scroll’ button together. Figure 1.20b Diagnostic alarms *If the user has disassembled and reassembled the instrument, this error can occur if any connectors are not seated properly. 2208e and 2204e Controller 1-27...
Page 36
Operation Installation and Operation Handbook 1-28 2208e and 2204e Controller...
Page 37
Installation and Operation Handbook Installation 2 Chapter 2 INSTALLATION 2 Chapter 2 INSTALLATION ..........1 INSTRUMENT LAYOUTS..............2 2.1.2 Outline Dimensions Model 2208e ............3 2.1.3 Outline Dimensions Model 2204e ............3 INTRODUCTION ................4 2.2.2 Controller labels ..................4 MECHANICAL INSTALLATION ............4 2.3.2 Unplugging and plugging-in the controller..........4 WIRING .....................5...
Installation and Operation Handbook INTRODUCTION The Models 2208e and 2204e are precision temperature controllers with self tuning. They have a modular hardware construction which provides two control outputs, two alarm relays and one communications port. Two logic inputs are provided as standard. In addition the Model 2204e has an optional plug-in 10A relay heating output.
Output 2 Common Output 3 Output 4 Pt100 Figure 2-5: Model 2208e wiring connections The ground connection is not required for electrical safety but must be connected to ensure EMC performance is optimised. *Do not use unused terminals as wire holders.
Output 4 Pt100 Figure 2-6: Model 2204e Wiring connections *The ground connection is not required for safety purposes but must be connected to ensure EMC performance is optimised. *Do not use unused terminals as wire holders. 2208e and 2204e Controller...
(18Vdc, 20mA max) in output 2 *Logic output can also be configured as logic input on module 2A. PDS Mode 1 & 2 are only supported in Module 1A. Figure 2-8: Outputs 1 and 2 connections 2208e and 2204e Controller...
When a relay contact is used in an alarm circuit ensure that the current passing through the snubber when the relay contact is open does not hold in low power electrical loads and thereby interfere with the failsafe operation of the alarm circuit. 2208e and 2204e Controller...
2-wire EIA-485 serial Do not Do not Common A (+) B (-) communications EIA-232 serial Not used Not used Common communications PDS Setpoint input Not used Not used Not used Signal Common Figure 2-10: Communication connections 2-10 2208e and 2204e Controller...
Series 2000™ Controller Note: All termination resistors are 220 ohm 1/4W carbon composition. Local grounds are at equipotential. Where equipotential is not available wire into separate zones using a galvanic isolator. Figure 2-11: 2-wire EIA-485 wiring 2208e and 2204e Controller 2-11...
Installation and Operation Handbook 2.10 DEVICENET WIRING TO SERIES 2200E CONTROLLERS This section covers the DeviceNet digital communications option for the model 2208e and 2204e PID controllers. To configure DeviceNet communications refer to pages 5-16 and 5-17. 2.10.2 DeviceNet Terminal Functions...
2200e Controller Network Supply 24Vdc ( +1%) 250mV p-p Ripple 121! (SLAVE) Address N+1 Daisy chain to further Fit to last instrument instruments in the chain Figure 2-12: 2-Wiring Connections for 2200e Series DeviceNet Controllers 2208e and 2204e Controller 2-13...
Page 50
Installation Installation and Operation Handbook 2-14 2208e and 2204e Controller...
3 Chapter 3 ACCESS LEVELS..........1 THE DIFFERENT ACCESS LEVELS ..........2 SELECTING AN ACCESS LEVEL ...........3 3.3.2 Returning to Operator Level..............5 Edit level...................5 3.4.2 Hiding or revealing a complete list ............6 3.4.3 Promoting a parameter .................6 2208e and 2204e Controller...
You can also promote parameters to the home list. (See Edit level at the end of the chapter). ConF Configuration This special level allows access to set up the fundamental characteristics of the controller. Figure 3-1 Access levels 2208e and 2204e Controller...
(If an incorrect password has been entered and the controller is still ‘locked’ then pressing Scroll at this point will simply return you to the aCCs list header.) Note: From this code display, you can access “read only” configuration level by pressing together. To escape, press together 2208e and 2204e Controller...
Press the Scroll button 3.2.6 Configuration level The first display of configuration is shown. See chapter 5, inSt Configuration for details of the configuration parameters. For instructions on leaving configuration level see Chapter 5, Configuration. ConF 2208e and 2204e Controller...
HidE Hides a parameter or list header. HidE HidE HidE For example: 2FSL The parameter selected is the set point for Alarm 2 - Full Scale Low ALtr It will be alterable in Operator level 2208e and 2204e Controller...
Scroll through the lists to the required parameter and choose the ‘Pro’ code. The parameter is then automatically added (promoted) into the Home display list (the parameter will also be accessible as normal from the standard lists. a maximum of 12 parameters can be promoted. Promoted parameters are automatically ‘alterable’. 2208e and 2204e Controller...
Page 57
4.3. How to Tune ..................4 4.3.1. Typical automatic tuning cycle ..............5 4.3.2. Calculation of the cutback values............5 4.4. MANUAL TUNING ................6 4.4.1. Setting the cutback values ..............7 4.4.2. Integrating action and manual reset............8 4.4.3. Automatic droop compensation (Adc) ...........8 2208e and 2204e Controller...
Relative cool Only present if cooling has been configured. Sets the cooling gain proportional band by dividing the Pb value by the rEL.C value. Table 4-1 Tuning parameters 2208e and 2204e Controller...
This method automatically determines the value of the parameters listed in table 4-1 on the previous page. The 2208e and 2204e use a ‘one-shot’ tuner which works by switching the output on and off to induce an oscillation in the measured value. From the amplitude and period of the oscillation, it calculates the tuning parameter values.
If you want ‘Proportional only’ or ‘PD’ or ‘PI’ control, you should set the ‘ti’ or ‘td’ parameters to OFF before commencing the tuning cycle. The tuner will leave them off and will not calculate a value for them. For valve position tuning and set-up, please refer to Appendix D. 2208e and 2204e Controller...
(for example, under startup conditions). If either low cutback or high cutback is set to ‘Auto’ the values will be fixed at three times the proportional band, and will not be changed during automatic tuning. 2208e and 2204e Controller...
Set the Pb, ti, td parameter values according to the calculations given in Table 4-2. Type of control Proportional Integral time ‘ti’ Derivative time band ‘Pb’ ‘td’ Proportional only P + I control 2.2xB 0.8xT P + I + D control 1.7xB 0.5xT 0.12xT Table 4-2 Tuning values 2208e and 2204e Controller...
In example (a) increase Lcb by the overshoot value. In example (b) reduce Lcb by the undershoot value. Example (a) Temperature Setpoint Overshoot Example (b) Temperature Undershoot Time Where the temperature approaches setpoint from above, you can set Hcb in a similar manner. 2208e and 2204e Controller...
Adc to ‘mAn’. Adc can be repeated as often as you require but between each adjustment you must allow time for the temperature to stabilise. 2208e and 2204e Controller...
Whenever the configuration menus are displayed or accessed all controller outputs are held at the power off state and control operation is suspended until exiting from configuration. 2208e and 2204e Controller...
At this point the controller is in 4th press configuration level Inst Inst Inst Inst ConF ConF ConF ConF ConF ConF ConF ConF Repeated pressing of “Page” button selects configuration list headings in a continuous loop Figure 5.1 2208e and 2204e Controller...
The actual parameters shown in your controller may differ slightly since some appear only as a result of selecting others. A full list of possibilities is included in the PARAMETER TABLES which follow the navigation diagram. 2208e and 2204e Controller...
BLoc Input Config. - selects the input sensor type Ltch User cal. Config. - to calibrate to external reference sources Alarms Config. - sets up the alarm types 2208e and 2204e Controller...
Func cnF.P HEAT COOL HEAt Baud SEnS SEnS SEnS See Table B 9600 parameter table, page 5- PrtY Out.L nonE SEnS RESn Out.H 100.0 See Table B VaL.L parameter table, page 5- VaL.H 100.0 Figure 5.4 2208e and 2204e Controller...
Page 70
Sets up the action of the fixed relay on output 3A 3A to 3C 4A Conf Sets the action of the 10A output relay in 2204 4A to 6D Pass Conf To choose new passwords Exit no/Yes To leave configuration level and return to operator level 2208e and 2204e Controller...
Freeze output (maintains output at value immediately before break) LC.Hi Load Current Scaling Factor See Chapter 9 Factory default parameter values and states are included where applicable and are indicated by the shaded areas in the following tables. 2208e and 2204e Controller...
Page 72
Appears for mV or V inputs only Auto Trip level set by the sensor input table Trip level set at 7.5KΩ HiHi Trip level set at 15KΩ (must be selected when voLt input is enabled) 2208e and 2204e Controller...
Page 73
‘Pnt.H’. This value is automatically calculated when performing a high point calibration. * If User calibration is enabled, then the User calibration parameters will appear in the Input list of Operator Full access level. See Chapter 6, User calibration. 2208e and 2204e Controller...
Page 74
(1) Blocking allows the alarm to become active only after it has first entered a safe state. These are ‘soft’ alarms, i.e. Indication only. They would normally be attached to an output. See Chapter 7 for a step by step guide. 5-10 2208e and 2204e Controller...
Page 75
Lock Key pad rset Reset StbY Standby - ALL outputs = OFF AmPS PDS load current input Logic input 2 configuration Functions Action on contact closure As per Logic input 1 except ‘AmPS’ not available 2208e and 2204e Controller 5-11...
Page 76
No parity EvEn Even parity Odd parity RESn FuLL Comms Resolution Full resolution Integer resolution Note 1: 1200 baud rate not supported by EIBisynch Note 2: Not used with some communication protocols. Please consult factory. 5-12 2208e and 2204e Controller...
Page 77
Normal (e.g.heating and cooling) Inverted (alarms - de-energise in alarm) DC output scaling For id = dC.OP the following parameters appear Out.L DC output minimum 0mA to 20mA Out.H DC output maximum 0mA to 20mA 2208e and 2204e Controller 5-13...
Page 78
A in the AL list: eg 1FSL = Full Scale Low If an alarm is not configured the displayed name will differ: e.g. ‘AL 1 will be shown, for the first alarm. 5-14 2208e and 2204e Controller...
Page 79
PASS PASS PASS Password list ACC.P FuLL or Edit level password cnF.P Configuration level Password Note:- When passwords are changed please make a note of the new numbers Exit Exit Exit Exit no/YES Exit Configuration 2208e and 2204e Controller 5-15...
Operation Handbook Configuration 5.14 CONFIGURATION OF DIGITAL COMMUNICATIONS The 2208e and 2204e controllers can be fitted with the following digital communications modules:- Protocol Module Fitted Order Code ModBus 2-wire RS485 4-wire RS422 RS232 EI-Bisynch 2-wire RS485 4-wire RS422...
The EDS (Electronic Data Sheet) file for the Series 2200e is named 2K2DN.EDS and is available from your supplier, or electronically by going to Web site (www.eurotherm.com). The EDS file is designed to automate the DeviceNet network configuration process by precisely defining vendor-specific and required device parameter information.
Page 82
Operation Handbook Configuration 5-18 2208e and 2204e Controller...
6 Chapter 6 USER CALIBRATION 6 Chapter 6 User calibration ..........1 What is the Purpose of User Calibration? ........2 User Calibration Enable ..............3 6.10 Single point calibration..............4 6.11 Two point calibration ..............5 6.12 Calibration points and Calibration offsets.........6 2208e and 2204e Controller...
Match the calibration of the controller to that of a particular transducer or sensor input Calibrate the controller to suit the characteristics of a particular installation. User calibration works by introducing zero and span offsets onto the factory set calibration. The factory set calibration can always be retrieved. 2208e and 2204e Controller...
Scroll button until you reach User calibration enable to select: YES: Calibration enable Calibration disabled Press together to go to the Exit display Exit Exit configuration to select ‘YES’ and return to Operator level. 2208e and 2204e Controller...
User parameters, as follows: Press the Scroll button Calibrate low point? CAL.S to select ‘YES’ Selecting ‘no’ will hide the next parameter Press the Scroll button continued on the next page 2208e and 2204e Controller...
Set the process under calibration such that the known reference exhibits the required higher Process Value (temperature) and allow to stabilize. Press the Scroll button to obtain the high calibration point as shown in the following diagrams. 2208e and 2204e Controller...
‘AdJ.H’ (adjust high calibration). Low point calibration offset Offset, in display units, at the user low calibration OFS.L point ‘Pnt.L High point calibration offset Offset, in display units, at the user high calibration OFS.H point ‘Pnt.H . 2208e and 2204e Controller...
The 2200e series controllers are capable of very sophisticated alarm strategies and, although setting up of alarms has already been covered in previous chapters, this section has been included to enable operators and commissioning engineers to design their own strategies for optimum plant operation. 2208e and 2204e Controller...
7.1.1 TYPES ALARMS The use of alarms in the 2208e and 2204e controllers is extremely versatile. Up to 4 alarms can be configured. Any combination of these 4 alarms can be attached to any one or more outputs, or any number of the available “soft” alarms can be combined to operate a single output.
Page 91
Sense Of Output Relay energised or de-energised in alarm condition. See also sections 1-12 and 7.4. Soft Alarms Indication only and do not operate an output. See also Section 1.11 for further information on alarm types. 2208e and 2204e Controller...
Signals the end of a program Program END Signals a new alarm New Alarm The Sense of the Output can be set to relay energised or de-energised in the alarm condition for any of the above functions. 2208e and 2204e Controller...
3F.S.H. 3FSH 3FSH 3FSH 3FSH Figure 7.2 to select: 1. inverted (relay de-energised SEnS SEnS SEnS SEnS in alarm) 2. direct (relay energised in alarm) Keep pressing “SCROLL” button to return to list header 2208e and 2204e Controller...
STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT In the previous example one alarm condition is allocated to one output relay. The 2208e and 2204e controllers allow alarms and events to be grouped on to a single output. These events are shown in the table below.
Page 96
Alarm Operation Installation and Operation Handbook 2208e and 2204e Controller...
Valve Position Installation and Operation Handbook 8.1. PARAMETERS FOR MOTORISED VALVE CONTROL The 2208e and 2204e can be configured for motorised valve control as an alternative to the standard PID control algorithm. This algorithm is designed specifically for positioning motorised valves.
Table 8-2 Valve Positioner Set-up Table The following operating parameters do not effect the 2200e when the valve positioner option has been configured: CYC.H Heat Cycle Time CYC.C Cool Cycle Time ont.C Minimum on time for cooling 2208e and 2204e Controller...
Page 100
Valve Position Installation and Operation Handbook 2208e and 2204e Controller...
To configure logic input a for pds (Mode 5 only) ......... 9 TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS ....10 9.9 TO ATTACH SOFT ALARMS TO A RELAY OUTPUT ....11 9.10 THE SCALING FACTOR ............12 9.10.1 To adjust the scaling factor ............12 2208e and 2204e Controller...
An alarm is shown if the PDS connection to Current Transformer Open Circuit PDCTX or SSR become disconnected An alarm is shown if the PDS connection Current Transformer Short Circuit from PDCTX or SSR are short circuited 2208e and 2204e Controller...
1. SSR type TE10/PDS2 OR 2. Intelligent current transformer type PD/CTX + contactor or zero voltage switching SSR 2208e or 2204e controller configured for PDS mode 2 option using logic output. This module must be fitted in module position 1. (order code M2).
1. Eurotherm intelligent current transformer type PD/CTX + contactor 2. 2208e or 2204e controller configured for PDS mode 5 option using logic, relay or triac output. This module must be fitted in module position 1. Digital input LA (order code M5) must be configured to accept PDCTX input as described in the configuration section of this appendix.
Meter mode applies to mode 5 only. If low current alarms are not configured the current displayed is a filtered instantaneous RMS value. This behaves like a damped analogue meter. It may be used in applications where the current sensor is not linked to control, for example, telemetry, indication. 2208e and 2204e Controller...
Ct.OP Current Indicates that the PDS input is open circuit. Transformer Mode 5 only. Open Circuit Ct.Sh Current Indicates that the PDS input is short circuit. Transformer Mode 5 only. Short Circuit 2208e and 2204e Controller...
, such as control. Any one or more alarms can be attached to an output, which will operate when an alarm occurs. Contacts are rated at 2A 264Vac for operating external beacons or audible devices. 2208e and 2204e Controller...
SSr1 to show SSr1 or is set to PDS mode SSr 2 as required. Press to show SEnS SEnS SEnS SEnS SEnS This sets the output signal to normal for heating control Press to show nor 2208e and 2204e Controller...
Press to select AmPs The system is designed to operate in either mode 2 or mode 5 configuration only. Selecting both simultaneously will disable the output. However, mode 1 and mode 5 may be used together. 2208e and 2204e Controller...
To make alarm 2 = has been accepted High Current Press to show HCr Note:- The above alarms are known as SOFT ALARMS because they are indication only. 9-10 2208e and 2204e Controller...
SS.r.F etc Alarms Connected to a Relay Output Soft SEnS Alarms Output Module until CLr appears in the lower display. To remove alarms from an output press This will clear all alarms attached to this output. 2208e and 2204e Controller 9-11...
Scalar = 100/N Where N = Turns through PDCTX Scalar Maximum Resolvable Current TE10 Determined by the maximum range of the SSR PDCTX 100A (or 100 ampere turns) Finally Exit configuration level. See Chapter 5. 9-12 2208e and 2204e Controller...
To configure retransmission............3 10.3 scaling retransmitted output signals ........4 To Range Retransmitted Output OP ..........4 10.1.1 To Range Retransmitted Setpoint SP or Process Variable PV..5 10.1.2 To Range Retransmitted Error Err..........5 10.1.3 2208e and 2204e Controller 10-1...
2. Setpoint 3. Error 4. Control Output The retransmission signal is available as 0-20mA, 4-20mA, 0-5V, 1-5V or 0-10V and is connected to terminals 1A and 1B when module 1A is fitted as a DC module. 10-2 2208e and 2204e Controller...
Retransmission parameter for Output demand retransmission Process Variable Error Setpoint (working) If Func is a retransmission Press to show SEns SEnS SEnS parameter the value SEnS SEnS of Sens has no effect. 2208e and 2204e Controller 10-3...
10.1.1 To Range Retransmitted Output OP For output of 0-100% = 0-20mA set Out.H to 20.0 and Out.L to 0.0 % Output For output of 0-100% = 4-20mA set Out.H to 20.0 and Out.L to 4.0 OUT.L OUT.H 10-4 2208e and 2204e Controller...
Retransmitted Value 0mA for an error of -10 0.0487mA for an error of 0 20mA for an error of +400 Note: To read a negative error it is necessary to set rnG.L to a negative limit 2208e and 2204e Controller 10-5...
Page 118
Retransmission Installation and Operation Handbook 10-6 2208e and 2204e Controller...
A Appendix A UNDERSTANDING THE ORDERING CODE The 2208e and 2204e controllers have a modular hardware construction with the option of four outputs and one communications port. Two logic inputs are provided as standard. In addition the Model 2204e has an optional plug-in 10A heating output.
Page 120
Table A PDS Input 4-20mA PID cooling Fitted unconfigured Setpoint DC Retrans. (isolated) PV retrans Select from table A Setpoint retrans Manual Output retrans No manual Error retrans English 0-20mA French 4-20mA German 0-5V Italian 1-5V 0-10V 2208e and 2204e Controller...
Page 121
9999 Cooling options 0 to 20mA -999 9999 Linear cooling 4 to 20ma -999 9999 Fan cooling 0 to 5Vdc -999 9999 Water cooling 1 to 5Vdc -999 9999 Oil cooling 0 to 10Vdc -999 9999 2208e and 2204e Controller...
Page 122
– up to one for temperature inputs, up to two for process inputs An external 1% current sense resistor is supplied as standard. If greater accuracy is required, a 0.1% 2.49Ω can be ordered as part number SUB2K/249R.1. 2208e and 2204e Controller...
In any case, avoid touching the exposed electronics of an instrument when withdrawing it from the sleeve. Failure to observe these precautions may cause damage to components of the instrument or some discomfort to the user. 2208e and 2204e Controller...
I/O while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs and outputs must be mains rated. 2208e and 2204e Controller...
Page 125
These units will typically include gas discharge tubes and metal oxide varistors that limit and control voltage transients on the supply line due to lightning strikes or inductive load switching. Devices are available in a range of energy ratings and should be selected to suit conditions at the installation. 2208e and 2204e Controller...
Page 126
Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit, with an independent temperature sensor, which will isolate the heating circuit. Please note that the alarm relays within the controller will not give protection under all failure conditions. 2208e and 2204e Controller...
Page 127
To minimise the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at both ends. In general keep cable lengths to a minimum. 2208e and 2204e Controller...
Triac Rating 1A, 30 to 264Vac resistive Application Heating or cooling High current Rating 10A, 264Vac resistive Application Heating Analog Range Isolated 0 to 20mA or 0 to 10Vdc (configurable between limits) Application Heating or cooling 2208e and 2204e Controller...
Page 129
PD control Alarms Types Full scale high or low. Deviation high, low, or band Modes Latching or non-latching. Normal or blocking action Up to four process alarms can be combined onto a single output 2208e and 2204e Controller...
Page 130
2.5kV) Atmospheres Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not suitable for use above 6,562ft (2000m) or in corrosive or explosive atmospheres without further protection. 2208e and 2204e Controller...
Page 132
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept HA026696...
Need help?
Do you have a question about the 2208e and is the answer not in the manual?
Questions and answers
how do I get the output 2 to come on? Recently had to swap out the card, I believe I got all the parameters switched over but the output 2 is not kicking on and I'm getting 3FSH fault. Any advice will be greatly appreciated
To enable output 2 on a Eurotherm 2208e after swapping out the card and resolving a 3FSH fault, follow these steps:
1. Ensure the correct I/O module for output 2 is physically installed.
2. Power cycle the controller if not already done.
3. Enter configuration mode on the controller.
4. Navigate to the I/O module setup section.
5. Configure output 2 settings as required (e.g., type, function).
6. Exit configuration mode and save settings.
The output should now be enabled and functional.
This answer is automatically generated