Input Current Control - Daikin SiBE07-618_D Service Manual Field

C-series inverter pair duct connected type
Table of Contents

Advertisement

Control Specification
3.5

Input Current Control

Outline
The microcomputer calculates the input current during the compressor is running, and sets the
frequency upper limit from the input current.
In case of heat pump model, this control which is the upper limit control of the frequency takes
priority to the lower limit of control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
Drooping zone
Keep zone
Reset zone
A (A)
B (A)
C (A)
Limitation of current drooping and stop value according to the outdoor temperature
34
A
B
C
After 2.5 seconds in this zone, the compressor is stopped.
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is pulled down by 2 Hz every second until it reaches the keep
zone.
The present maximum frequency goes on.
Limit of the frequency is canceled.
50 class
Cooling
20.0
10.0
9.0
The current droops when outdoor temperature becomes higher than a certain level
(depending on the model).
Compressor Stop
60 class
Heating
Cooling
20.0
15.0
12.0
14.0
11.0
SiBE07-618_D
Stop Zone
Drooping Zone
Keep Zone
Reset Zone
(R4304)
Heating
16.0
15.0
Function and Control