Forced Cooling Operation Mode - Daikin SiBE07-618_D Service Manual Field

C-series inverter pair duct connected type
Table of Contents

Advertisement

Forced Cooling Operation Mode

2. Forced Cooling Operation Mode

Outline
Forced cooling operation mode includes only forced cooling.
Detail
Conditions
Start
Command
frequency
End
Others
128
Item
Forced Cooling
1) The outdoor unit is not abnormal
and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
cooling
The forced
allowed when the above both
conditions are met.
Press the forced
ON/OFF button (SW1) on the indoor
unit for 5 seconds.
66 Hz
1) Press the forced
ON/OFF button (SW1) on the indoor
unit again.
2) Press the ON/OFF button on the
remote controller.
3) The operation ends automatically
after 15 minutes.
The protection functions are prior to all
others in the forced
operation is
cooling
operation
cooling
operation
cooling
operation.
ON/OFF button
(SW1)
(R14086)
SiBE07-618_D