4.23 Refrigerant Shortage

U0
Remote
Controller
Display
Method of
Refrigerant shortage detection I:
Malfunction
Refrigerant shortage is detected by checking the input current value and the compressor output
frequency. If the refrigerant is short, the input current is smaller than the normal value.
Detection
Refrigerant shortage detection II:
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends
to rise.
Malfunction
Refrigerant shortage detection I:
Decision
The following conditions continue for 7 minutes.
Conditions
Refrigerant shortage detection II:
The following conditions continue for 80 seconds.
Supposed
Causes
Service Diagnosis
DC current ≤ A × Output frequency + B
Output frequency > C
A
B
(–)
(A)
18/1000
0.7
Target opening of the electronic expansion valve ≥ D
Discharge pipe temperature > E × target discharge pipe temperature + F
D
(pulse)
50 class
480
60 class
480
If the error repeats 4 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
room or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective electronic expansion valve
C
(Hz)
55
E
F (°C)
(–)
128/128
Cooling: 20, Heating: 45
128/128
Cooling: 60, Heating: 45
Troubleshooting