DEFROST BOARD DIAGNOSTICS
See table 10 to determine defrost board operational conditions and to diagnose cause and solution to problems.
Table 10. Defrost Control Board Diagnostic
LEDs
DS2
DSl
Condition/Code
Possible
Cause(s)
Solution
Green
Red
1 Check control transformer power (24V).
No power (24V) to board terminals R
2 If power is available to board and LED(s) do not
OFF
OFF
Power problem
and C or board failure.
light, replace board.
Simultaneous
Unit operating normally or in standby
SLOW Flash
Normal operation
mode.
None required.
Alternating SLOW
5-minute anti-short cycle
Initial power up, safety trip, end of
None required (Jumper TEST pins to override)
Flash
delay
room thermostat demand.
Simultaneous
Sensor being detected open or shorted or out of temperature range. Board will revert to time/
FAST Flash
Ambient Sensor Problem
temperature defrost operation. (System will still heat or cool).
Alternating
Coil Sensor Problem
Sensor being detected open or shorted or out of temperature range. Board will not perform
FAST Flash
demand or time/temperature
defrost operation. (System will still heat or cool).
ON
Indicates that board has internal component failure. Cycle 24 volt power to board. If code does
ON
Circuit Board Failure
not clear, replace board.
FAULT and LOCKOUT CODES
(Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
SLOW
OFF
Low Pressure Fault
Flash
OFF
ON
Low Pressure LOCKOUT
SLOW
Flash
OFF
High Pressure Fault
ON
OFF
High Pressure LOCKOUT
SLOW
Discharge Line Temperature
Flash
ON
Fault
FAST
Discharge Line Temperature
Flash
ON
LOCKOUT
Fast
Flash
Discharge Sensor Fault
OFF
Discharge Sensor
LOCKOUT
1 Restricted air flow over indoor or
outdoor coil.
2 Improper refrigerant charge in
system,
3 Improper metering device installed or
incorrect operation of metering
device,
4 Incorrect or improper sensor location
or connection to system.
1 Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan motor for
proper current draws.
2 Check system charge using approach and subcool-
ing temperatures,
3 Check system operating pressures and compare to
unit charging charts.
4 Make sure all pressure switches and sensors have
secure connections
to system to prevent refrigerant
leaks or errors in pressure and temperature mea-
surements.
This model does not have a defrost line sensor, therefore this code is not applicable.
The XP14 series units does not use a defrost line sensor, However, a resistor is installed
OFF
across pins P4-1 and P4-2. If the resistor is missing or damage then this fault code will be
displayed.
Fast
Flash
This model does not have a defrost line sensor, therefore this code is not applicable.
Table 11. Sensor Temperature/Resistance
Range
Sensor
Temperature
Range °F (°C)
Resistance Values Range (ohms)
Pins/Wire Color
Outdoor (Ambient)
-35 to 120 (-37) to (48)
280,000 to 3750
3 and 4 (Black)
Coil
-35 to 120 (-37) to (48)
280,000 to 3750
5 and 6 (Brown)
Note: Sensor resistance decreases as sensed temperature increases (see figure 26).
5750
m, 7450
lOO
90
8o
70
|
11775
60 |B
15425
50
_119975
26200
30
[] 34375
w
20
m46275
III
10
62700
85300
o
I
I
10000
30000
50000
70000
90000
RESISTANCE(OHMS)
Figure 26. Ambient and Coil Sensors
Page 22
505244M
04/08