Step 1. Determine the desired DT--Measure
entering air tempera-
ture using dry bulb (A) and wet bulb (B) DT is the intersecting value of
A and B in the table (see triangle)
Step 2. Find temperature
drop across ceil--Measure
the coil's dry
bulb entering and leaving air temperatures
(A and C). Temperature
Drop Formula: (TDrop) = A minus C.
Step 3. Determine
if fan needs adjustment--If
the difference be-
tween the measured TDrop and the desired DT (TDropiDT) is within
+3 °, no adjustment is needed. See examples: Assume DT = 15 and A
temp. = 72 °, these C temperatures would necessitate stated actions:
C °
TDrop-
DT
=
°F
ACTION
53°
19
15
=
4
Increase the airflow
58°
14
15
=
-1
(within +3 ° range) no change
62 °
10
15
=
-5
Decrease the airflow
Step 4. Adjust the fan speed--See
indoor unit instructions to in-
crease/decrease
fan speed
Changing air flow affects all temperatures;
recheck temperatures to
confirm that the temperature drop and DT are within +3 °.
Figure 23. Checking
Indoor Airflow over Evaporator Coil using Delta-T Chart
SETUP FOR CHARGING
Connect the manifold gauge set to the unit's service ports
(see figure 20):
low pressure gauge to vapor service port
high pressure gauge to liquid service port
Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC-410A,
CALCULATING
CHARGE
If the system is void of refrigerant, first, locate and repair
any leaks and then weigh in the refrigerant charge into the
unit, To calculate the total refrigerant charge:
Amount
Adjust amt. for
Additional charge
specified
variation in
specified per
on
line set length
indoor unit match-up
Total
nameplate
(table 6)
(table 7)
charge
+
+
=
Page 16