Lennox XP14 Elite Series Installation Instructions Manual page 17

Xp14 elite series heat pumps
Hide thumbs Also See for XP14 Elite Series:

Advertisement

IMPORTANT
Table 5. Normal Operating Pressures - Liquid +10 and Vapor +5 PSIG* (Cooling)
XP14-018
XP14-024
XP14-030
XP14-036
XP14-042
XP14-048
XP14-060
Liquid/
Liquid/
Liquid/
Liquid/
Liquid/
Liquid/
Liquid/
°F (°C)**
Vapor
Vapor
Vapor
Vapor
Vapor
Vapor
Vapor
Heating
60 (15)
346 / 139
352 / 138
338 / 137
350 / 134
373 / 139
355 / 130
351 / 117
50 (10)
323 / 117
331 / 114
334 / 112
331 / 117
363 / 117
336 / 113
333 / 105
40 (4)
306 / 98
304 / 99
312 / 93
313 / 97
348 / 97
315 / 88
316 / 88
30 (-1)
278 / 84
299 / 80
302 / 74
298 / 83
336 / 74
296 / 72
308 / 70
20 (-7)
273 / 66
283 / 66
280 / 53
284 / 66
322 / 64
286 / 64
300 / 61
Cooling
65 (18)
226 / 140
233 / 137
238 / 138
220 / 138
223 / 125
231 / 136
243 / 136
70 (21)
244 / 141
252 / 138
263 / 139
236 / 140
241 / 130
248 / 139
263 / 137
75 (24)
263 / 142
271 / 140
279 / 139
256 / 141
261 / 134
271 / 140
282 / 138
80 (27)
283 / 143
292 / 141
299 / 140
276 / 142
282 / 138
291 / 142
306 / 139
85 (29)
302 / 144
314 / 142
324 / 141
298 / 143
302 / 139
312 / 143
327 / 140
90 (32)
328 / 145
338 / 143
340 / 142
321 / 144
326 / 140
335 / 144
351 / 141
95 (35)
351 / 146
361 / 145
375 / 145
344 / 144
349 / 141
359 / 145
376 / 142
100 (38)
376 / 147
387 / 146
397 / 145
369 / 146
374 / 142
384 / 146
401 / 143
105 (41)
402 / 148
412 / 147
424 / 147
394 / 147
399 / 143
411 / 148
426 / 145
110 (38)
430 / 149
441 / 148
454 / 150
421 / 148
428 / 145
439 / 149
452 / 146
115 (45)
465 / 150
471 / 151
485 / 150
449 / 149
455 / 146
468 / 150
484 / 148
*IMPORTANT--These
are most popular match-up pressures. Indoor match up, indoor air quality, and indoor
load cause pressures to vary.
**Temperature
of the air entering the outside coil.
1. Recover the refrigerant from the unit,
2. Conduct leak check; evacuate as previously outlined,
3, Weigh in the unit nameplate charge plus any charge
required for line set differences from 15 feet and any
extra indoor unit match-up amount per table 7, (If
weighing
facilities
are
not
available,
use
the
subcooling method,)
Table 6. Charge per Line Set Lengths
Liquid Line
Oz. per 5 ft. (g per 1.5m) adjust from
Set Diameter
15 ft. (4.6m) line set*
3/8 in. (9.5mm)
3 ounce
per 5 ft. (85g per 1.5m)
NOTE - *if line length is greater than 15 ft. (4.6 m), add this amount, If
line length is less than 15 ft. (4.6 m), subtract this amount.
Requirements--these
items are required for charging:
Manifold gauge set connected to unit.
Thermometers for measuring outdoor ambient, liquid
line, and vapor line temperatures,
When
to
use
cooling
mode--When
outdoor
temperature is 60°F (15°C) and above, use cooling mode
to adjust charge,
When
to
use
heating
mode--When
the
outdoor
temperature is below 60°F (15°C), use the heating mode to
adjust the charge,
Adding
Charge for Indoor
Match-Up--Table
7 lists all
the Lennox recommended indoor unit matches along with
the charge levels for the various sizes of outdoor units,
Page 17
XP14 SERIES