Parameter Name
36
Frequency jump 3B
37
Speed display
Up-to-frequency
41
sensitivity
Output frequency
42
detection
Output frequency
43
detection for reverse
rotation
Second acceleration/
44
deceleration time
Second deceleration
45
time
46
Second torque boost
Second V/F
47
(base frequency)
Second stall
48
prevention operation
current
Second stall
49
prevention operation
frequency
Second output
50
frequency detection
Second electronic
51
thermal O/L relay
DU/PU main display
52
data selection
CA terminal function
54
selection
Frequency
55
monitoring reference
Current monitoring
56
reference
57
Restart coasting time
58
Restart cushion time
Remote function
59
selection
Energy saving
60
control selection
65
Retry selection
Stall prevention
66
operation reduction
starting frequency
*1
The setting depends on capacities. (01160 or less/01800 or more)
*2
Setting of "9" can be made for the 01800 or more.
*3
Setting can be made for the 01800 or more.
*4
Setting of "100 to 103", "114 to 117" can be made for the 01800 or more.
Initial
Setting Range
Value
0 to 400Hz,
9999
9999
0, 1 to 9998
0
0 to 100%
10%
0 to 400Hz
6Hz
0 to 400Hz,
9999
9999
0 to 3600/360s
5s
0 to 3600/360s,
9999
9999
0 to 30%, 9999
9999
0 to 400Hz,
9999
9999
0 to 120%
110%
0 to 400Hz,
9999
0Hz
0 to 400Hz
30Hz
0 to 500A,
9999/
9999
0 to 3600A,
1
9999 *
0, 5, 6, 8 to 14,
17, 20, 23 to 25,
0
50 to 57, 64, 67,
2
81 to 86, 100 *
1 to 3, 5, 6,
8 to 14, 17, 21,
1
24, 50, 52, 53,
67, 70, 85 *2
0 to 400Hz
50Hz
0 to 500A/
Rated
1
inverter
0 to 3600A *
current
0, 0.1 to 5s,
9999/
9999
0, 0.1 to 30s,
1
9999 *
0 to 60s
1s
0, 1, 2, 3, 11, 12,
0
13
0, 4, 9
0
0 to 5
0
0 to 400Hz
50Hz
Parameter Name
Number of retries at
67
alarm occurrence
68
Retry waiting time
Retry count display
69
erase
Special regenerative
70
3
brake duty *
71
Applied motor
PWM frequency
72
selection
Analog input
73
selection
Input filter time
74
constant
Reset selection/
disconnected PU
75
detection/PU stop
selection
Alarm code output
76
selection
Parameter write
77
selection
Reverse rotation
78
prevention selection
Operation mode
79
selection
80
Motor capacity
90
Motor constant (R1)
100
V/F1 (first frequency)
V/F1 (first frequency
101
voltage)
V/F2
102
(second frequency)
V/F2 (second
103
frequency voltage)
V/F3
104
(third frequency)
V/F3 (third frequency
105
voltage)
V/F4
106
(fourth frequency)
V/F4 (fourth
107
frequency voltage)
108
V/F5 (fifth frequency)
V/F5 (fifth frequency
109
voltage)
PU communication
117
station number
PARAMETER
Initial
Setting Range
Value
0, 1 to 10,
0
101 to 110
0 to 10s
1s
0
0
0 to 10%
0%
0, 1, 2, 20
0
0 to 15/
2
1
0 to 6, 25 *
0 to 7, 10 to 17
1
0 to 8
1
0 to 3, 14 to 17,
100 to 103,
14
4
114 to 117 *
0, 1, 2
0
0, 1, 2
0
0, 1, 2
0
0, 1, 2, 3, 4, 6, 7
0
0.4 to 55kW,
9999/
9999
0 to 3600kW,
1
9999 *
0 to 50Ω, 9999/
0 to 400mΩ,
9999
1
9999 *
0 to 400Hz,
9999
9999
0 to 1000V
0V
0 to 400Hz,
9999
9999
0 to 1000V
0V
0 to 400Hz,
9999
9999
0 to 1000V
0V
0 to 400Hz,
9999
9999
0 to 1000V
0V
0 to 400Hz,
9999
9999
0 to 1000V
0V
0 to 31
0
15