Mitsubishi Electric FR-F740-00023 Installation Manuallines page 12

Fr-f700 series
Hide thumbs Also See for FR-F740-00023:
Table of Contents

Advertisement

WIRING
FR-F740-03250, 03610-EC
L1 L2
L3
Power
supply
Screw size
M12
(for Option)
FR-F740-05470 to 12120-EC
L1 L2
L3
Power
supply
CAUTION
The power supply cables must be connected to R/L1, S/L2, T/L3. Never connect the power cable to the U, V, W, of the
inverter. Doing so will damaged the inverter. (Phase sequence needs not to be matched.)
Connect the motor to U, V, W. At this time turning on the forward rotation switch (signal) rotates the motor in the
counterclockwise direction when viewed from the motor shaft.
When wiring the inverter main circuit conductor of the 05470 or more, tighten a
nut from the right side of the conductor. When wiring two wires, place wires on
both sides of the conductor (refer to the drawing). For wiring, use bolts (nuts)
provided with the inverter.
6
Screw size
(M4)
Charge lamp
Jumper
Screw size
(M10)
M
3 ~
Motor
DC reactor
Screw size
M4
Charge lamp
Jumper
Screw size
(M12)
M
3~
Motor
DC reactor
Screw size
(M10)
FR-F740-04320, 04810-EC
L1 L2
L3
Power
supply
Screw size
M12
(for Option)
Screw size
(M4)
Charge lamp
Jumper
Screw size
(M12)
Screw size
(M10)
M
3~
Motor
DC reactor