Download  Print this page

Parameter; Parameter List - Mitsubishi Electric FR-F740-00023 Installation Manuallines

Fr-f700 series.
Hide thumbs

Advertisement

6 PARAMETER

6.1 Parameter list

In the initial setting, only the simple mode parameters are displayed.
Set Pr. 160 User group read selection as required.
Parameter
Name
User group read selection
160
Remarks
The parameters marked
The parameters marked with
(initial value) is set in Pr. 77 Parameter write selection.
Parameter Name
0
Torque boost
1
Maximum frequency
2
Minimum frequency
3
Base frequency
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
7
Acceleration time
8
Deceleration time
Electronic thermal
9
O/L relay
DC injection brake
10
operation frequency
DC injection brake
11
operation time
DC injection brake
12
operation voltage
13
Starting frequency
Load pattern
14
selection
15
Jog frequency
Jog acceleration/
16
deceleration time
17
MRS input selection
High speed
18
maximum frequency
*1
The setting depends on capacities. (01160 or less/01800 or more)
*2
The setting depends on capacities. (00023/00038 to 00083/00126, 00170/00250 to 00770/00930, 01160/01800 or more)
*3
The setting depends on capacities. (00170 or less/00250 or more)
*4
The setting depends on capacities. (00170 or less/00250 to 01160/01800 or more).
14
Initial
Setting
Value
Range
9999
are the simple mode parameters.
in the table allow its setting to be changed during operation even if "0"
Initial
Setting Range
Value
0 to 30%
6/4/3/2/
1.5/1% *
0 to 120Hz
120/60Hz *
0 to 120Hz
0Hz
0 to 400Hz
50Hz
0 to 400Hz
50Hz
0 to 400Hz
30Hz
0 to 400Hz
10Hz
0 to 3600/360s
5s/15s *
0 to 3600/360s
10s/30s *
0 to 500/
Rated
1
inverter
0 to 3600A *
current
0 to 120Hz,
3Hz
9999
0 to 10s, 8888
0.5s
0 to 30%
4/2/1% *
0 to 60Hz
0.5Hz
0, 1
1
0 to 400Hz
5Hz
0 to 3600/360s
0.5s
0, 2
0
120 to 400Hz
120/60Hz *
Remarks
9999
Only the simple mode parameters can be displayed.
Simple mode and extended mode parameters can be
0
displayed.
1
Only parameters registered in the user group can be displayed.
Parameter Name
Base frequency
19
2
voltage
1
Acceleration/
20
deceleration
reference frequency
Acceleration/
21
deceleration time
increments
Stall prevention
22
operation level
Stall prevention
operation level
23
compensation factor
3
at double speed
3
Multi-speed setting
24 to 27
(4 speed to 7 speed)
Multi-speed input
28
compensation
selection
Acceleration/
29
deceleration pattern
selection
4
Regenerative
30
function selection
31
Frequency jump 1A
32
Frequency jump 1B
33
Frequency jump 2A
34
Frequency jump 2B
1
35
Frequency jump 3A
Initial
Setting Range
Value
0 to 1000V,
8888
8888, 9999
1 to 400Hz
50Hz
0, 1
0
0 to 120%, 9999
110%
0 to 150%, 9999
9999
0 to 400Hz,
9999
9999
0, 1
0
0, 1, 2, 3, 6
0
0, 2, 10, 20, 100,
120/
0, 1, 2, 10, 11,
0
20, 21, 100, 101,
1
120, 121 *
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999

Advertisement

Comments to this Manuals

Symbols: 0
Latest comments: