Summary of Contents for SystemAir Danvent DV

  • Page 1 Danvent DV, Danvent TIME Air Handling Units User Manual...
  • Page 3: Description Of The Air Handling Units

    Introduction Detailed table of contents on the following pages 1. Manufacturer 2. Declaration of conformity 3. Description of the air handling units 4. Intended use, noise and vibration 5. Protection and safety measures 6. Electrical connection 7. Plumbing 8. Accompanying documents 9.
  • Page 4: Table Of Contents

    Contents 1. MANUFACTURER ..................................8 1.1 Manufacturer, supplier data .......................... 8 1.2 Name of machines ............................8 2. DECLARATION OF CONFORMITY ............................9 3. DESCRIPTION OF THE AIR HANDLING UNITS – 8 MODELS ..................10 3.1 Common for all air handling unit models ...................... 10 3.2 Specific data about each model of the air handling unit –...
  • Page 5: Protection And Safety Measures

    4.7 Prohibited use of the machine ........................21 4.8 Noise and vibration ............................21 5. PROTECTION AND SAFETY MEASURES .......................... 22 5.1 Protection measures and additional protection measures ................22 5.2 Necessary protection measures prior to start-up..................22 5.2.1. Design of protection measures ........................22 5.2.2.
  • Page 6 6.4.15 Damper motors ............................. 27 6.4.16 Filter guards..............................27 6.4.17 Room temperature sensors ........................... 27 6.4.18 Frost protection ............................. 28 6.4.19 Systemair Control Panel ..........................28 6.4.20 Cooling recovery ............................28 6.4.21 Free cooling ..............................28 6.4.22 Alarm signal ..............................28 6.4.23 Heat recovery ..............................
  • Page 7 10. COMMISSIONING ................................. 33 11. DVU - WIRING DIAGRAM FOR INTERNAL CONTROLLER IN THE DVU SECTION ..........34 12. MENU FOR INTERNAL CONTROLLER IN THE DVU SECTION ................. 35...
  • Page 8: Manufacturer

    This User Manual covers all air handling units delivered by Systemair A/S. Manufacturer and supplier data: Systemair A/S Ved Milepælen 7 DK-8361 Hasselager Responsible: Ulf Bang 1.2 Name of machines This manual is about Systemair air handling units called Danvent DV Units and Danvent TIME Units.
  • Page 9: Declaration Of Conformity

    Systemair A/S Ved Milepælen 7 DK - 8361 Hasselager hereby declares that air handling units of the flowing types: DANVENT DV delivered without control systems DANVENT DV delivered with control systems TIME are manufactured and delivered in accordance with following directives:...
  • Page 10: Electrical Connection

    3.1 Common for all air handling unit models All Danvent DV and TIME air handling units are manufactured in compliance with the EC Declaration of Conformity and they are CE marked as machines. If the buyer carries out changes or adds components in or on the machine, the buyer must issue a new EC Declaration of Conformity and a new CE marking of the machine.
  • Page 11: Time Unit - Outdoor Model

    This model of the DV unit has an integrated control system and depending on the size of the unit, the switchboard is installed on the unit or on the front of the unit. The intelligent controller - Systemair E28 – is mounted in the switchboard, and all electrical connections between switchboard and components in the unit are installed.
  • Page 12: Dv Unit With Switchboard/Control System - Delivered As One Section On Base Frame

    The Systemair Control Panel with 10 meters of cable is not connected to the controller in the switchboard. All external components delivered are packed in a cardboard box delivered together with the unit.
  • Page 13: Dv Unit With Switchboard And Control Components, Without Controller - Delivered As One Section On Base Frame

    The Systemair Control Panel with 10 meters of cable is not connected to the controller in the switchboard. All external components delivered are packed in a cardboard box delivered together with the unit.
  • Page 14: Dvu - Section (Cooling Unit)

    The Systemair Control Panel with 10 meters of cable is not connected to the controller in the switchboard. All external components delivered are packed in a cardboard box delivered together with the unit.
  • Page 15 Extract Supply CapReg Analog in Relay Digital- 3*400 RS485 Relay- Analog- Relay On/of Digital in Alarm Alarm out 3.2.8.1 Using the control panel of the DVU-internal controller for the cooling compressor system Two LEDs (light diodes) are placed on the DVU-internal controller and each of the LEDs can be on or flash green, red or orange.
  • Page 16 3.2.8.2 Background illumination of the display Background illumination of the display switches on automatically when the potentiometer is turned or pressed. The illumination switches off one minute after the last activation of the potentiometer. By alarm the illumination flashes until the alarm is acknowledged 3.2.8.3 Potentiometer on the internal controller for the cooling compressor system The potentiometer is the only tool for the selection of menus and for changing parameters in the DVU- internal controller.
  • Page 17 3.2.8.11 Hotgas – setting of period This is the number of seconds that the hotgas valve is open. The period is relatively long, but the supply temperature is not oscillating at all and the stability of the supply temperature is sufficient. The number of seconds is a factory setting that should not be reduced.
  • Page 18 Especially for compressor VTZ 121 in DVU 25 and DVU 30 In addition to the above-mentioned modifications, the modifications below are necessary for the compressor VTZ 121 in DVU 25 and DVU 30; Value in menu item 1-90 changed to 2 Value in menu item 1-93 Terminal 54 changed to 2 Usually the Danfoss frequency converter keeps the change to the standard factory setting stored for ever, but if the software has been turned back to the original factory setting for some reason, the above-...
  • Page 19 90 Hz. If the temperature and humidity conditions on the site deviate from the above- mentioned conditions, accurate values can be calculated in the design programme SystemairCAD. Systemair is ready to provide you with a print-out, if a copy of calculation of the specific unit in the SystemairCAD is not available.
  • Page 20: Intended Use, Noise And Vibration

    4. Intended use, noise and vibration 4.1. Intended use and range of applications The air handling units are intended for the transport and treatment of air between -40 °C and + 60 °C The units are exclusively for comfort ventilation and not for air that causes severe corrosion to galvanized steel and to copper and aluminum.
  • Page 21: Dvu - Cooling System

    The noise of the unit can exceed 70 DB. Order-specific noise data are delivered on a separate sheet with the Transport and Installation Manual. Calculations of noise data for other conditions are available in the Systemair CAD software by Systemair.
  • Page 22: Protection And Safety Measures

    5. Protection and safety measures 5.1 Protection measures and additional protection measures The units are provided with guards to avoid unintended hazards and injury because of rotating parts in the unit. The potential sources of harm are the fans with fast rotating impellers. Hazards from the impellers are obvious during operation, but when power is cut-off, the impellers are still potential hazards due to after-run for at least 20 seconds.
  • Page 23: Electrical Installation

    Helmet • Particulate respirator – maintenance free including foam face-seal and adjustable pre-threaded • headbands – for replacing filters. Padlock for locking the supply disconnecting device in the off position • 6. Electrical installation 6.1 Description The components are mounted as well as possible in all models of the air handling units. All models are listed in section 3.
  • Page 24: Installation Of Mains Power Supply

    When the unit is running at reduced speed or is in shutdown mode, it can be forced up one step by using a Push button (impulse). The required number of minutes for the extended operation must be selected on the Systemair Control Panel. Button and cable are not delivered by Systemair...
  • Page 25: Valve And Valve Motor For Heating Coil

    6.4.6 Circulation pump, heating Circulation pump is not included in the delivery from Systemair. If the pump has not been activated for 24 hours, the pump is exercised once daily for 1 minute to keep the pump in a good condition. Cables are not delivered by Systemair.
  • Page 26: Communication With Bms Systems

    MODBUS, another version is prepared for EXO4 communication via TCP/IP, a third version is prepared for LON communication. Special set-up of the controller for communication with the BMS system is not included in the delivery from Systemair. 6.4.9 E tool programme The installer can download the PC software called E tool from www.regin.se...
  • Page 27: Pressure Transmitters

    6.4.16 Filter guards Filter guard over prefilter and primary filter installed and connected to the controller for display of alarm when the mechanically set limit is exceeded. Filter alarm will be displayed on the Systemair Control Panel. 6.4.17 Room temperature sensors One or two external room temperature sensors are available.
  • Page 28: Frost Protection

    6.4.19 Systemair Control Panel The separate cable-connected (10m) hand terminal with display and buttons – the Systemair Control Panel – is always necessary for the normal handling and programming, because the controller – Systemair E28 – is without display and buttons.
  • Page 29: Plumbing

    Pipes, insulation, electrical heating wires, control system for heating wires and circulation pump are not delivered by Systemair. 7.4.2 Cooling coils Pipes for cooling must be protected by insulation against condensation on the pipes and loss of cooling in the summer.
  • Page 30: Draining Condensate Water

    Systemair delivered by Systemair delivered by Systemair delivered by Systemair delivered by Systemair delivered by Systemair delivered by Systemair delivered by Systemair delivered by Systemair).
  • Page 31: Draining Condensate Water From Cooling Battery

    7.7 Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from Draining condensate water from...
  • Page 32: Dv Units With Switchboard And Control Components - Without Controller

    Components in the control system Vacon frequency converter • Corrigo manuals • Damper motors • Filter guards • Temperature sensors • Fire thermostats • Smoke detectors • Pressure transmitters • Valves • Valve motors • CO2 sensor • Systemair Control Panel • Others •...
  • Page 33: Start-Up

    Switch on power and the unit should be ready for the start-up. 9.1.3 Enter relevant values in the controller Units with control system are controlled from the Systemair Control Panel. Enter the relevant values in controller. 10. Commissioning...
  • Page 34: Dvu - Wiring Diagram For Internal Controller

    11. DVU - wiring diagram for internal controller in the DVU section...
  • Page 35: Menu For Internal Controller In The Dvu

    12. Menu for internal controller in the DVU section Menupoint Submenu Submenu Default Comments In: nnn% Set point for capacity level Out: nnn% Actual capacity level SETTINGS MENU UP Number of automatic resets of high pressure switch AUTORES. off’s within one hour before activation of alarm. POLARITY Polarity of BMS set to “Normally Open”...
  • Page 36 Systemair A/S, Ved Milepælen 7, 8361 Hasselager...