Setting the Bar Code Reader Input Function

6-10 Setting the Bar Code Reader Input Function

Reference:
Communications Condition Settings for Bar Code Readers
Setting Item
Data bit length
Sets the bit length for the data bits.
Stop bit length
Sets the stop bit length for the data.
Parity bit
Sets the parity bit for the data.
Communications
Sets the communications speed for the bar code reader
speed
Input method
Sets the method for confirming data when it is input to a charac-
ter string input field.
Manual: The data is confirmed with a touch switch. The data can
be corrected and character strings can be added.
Auto: The data is automatically confirmed when it is input.
Setting the Communications Conditions and Setting Method
The NT31/NT31C has a bar code reader input function which allows a bar
code reader to be connected and bar code data to read as character strings
into character string input fields.
This section describes the communications conditions for the bar code reader
and the setting method for confirming the input data.
• For details on bar code reader types and connection methods, refer to 3-4
Connecting a Bar Code Reader in this manual and for details on how to
use a bar code reader refer to 3-7 Input of Numeric Values and Character
Strings in the Reference Manual.
• The bar code reader is connected to serial port A. This means that serial
port B must be used for communications with the host.
Function
* Default (factory) setting
Set the bar code reader communications conditions and method of confirma-
tion at input by following the menu operation from the System Menu shown
below.
Ver 4.12
Setting Options
7* or 8 bits
1 or 2* bits
None, odd, even*
4800, 9600*, or 19200
bps
Manual*, Auto
Select Maintenance Mode.
Select Memory Switch.
Section 6-10
Page
189
189