I. CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
PRIMARY
STATE
MESSAGE
259
PROTECTIVE LIMIT CCN OVERRIDE STOP
282
PROTECTIVE LIMIT INVALID VFD CONFIG
283
PROTECTIVE LIMIT INVALID VFD CONFIG
284
VFD GATEWAY
285
VFD GATEWAY
286
PROTECTIVE LIMIT INVERTER
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
J. CHILLER ALERTS
ICVC FAULT
PRIMARY
STATE
MESSAGE
140
SENSOR ALERT
141
SENSOR ALERT
142
LOW OIL
PRESSURE ALERT
143
AUTORESTART
PENDING
144
AUTORESTART
PENDING
145
AUTORESTART
PENDING
146
AUTORESTART
PENDING
147
AUTORESTART
PENDING
148
AUTORESTART
PENDING
149
SENSOR ALERT
150
SENSOR ALERT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 16 — Alarm and Alert Messages (cont)
SECONDARY
MESSAGE
259→CCN Emergency/
Override Stop.
282→Line Frequency
[VALUE] Exceeded Configura-
tion Range.
283→Compressor 100%
Speed Config Ranges: 50=Hz
45-52; 60 Hz=55-62.
COMPATIBILITY
284→VFD Gateway Compati-
CONFLICT
bility Conflict: Check VFG/
VFD Versions.
COMPATIBILITY
285→VFD Gateway Compati-
CONFLICT
bility Conflict: Check VFG/
ICVC Versions.
286→Inverter Overcurrent
OVERCURRENT
Fault: Check VFD Status.
SECONDARY
MESSAGE
LEAVING COND WATER
140→Sensor Fault: Check
TEMP
Leaving Cond Water Sensor.
ENTERING COND WATER
141→Sensor Fault: Check
TEMP
Entering Cond Water Sensor.
CHECK OIL FILTER
142→Low Oil Pressure Alert.
Check Oil Filter.
LINE CURRENT
143→Line Current Imbal-
IMBALANCE
ance: Check VFD Fault His-
tory for Values.
LINE VOLTAGE
144→Single Cycle Line
DROP OUT
Voltage Dropout.
HIGH LINE VOLTAGE
145→High Percent Line
Voltage [VALUE].
LOW LINE VOLTAGE
146→Low Percent Line
Voltage [VALUE].
VFD MODULE RESET
147->VFD Module Power-On
Reset When Running.
POWER LOSS
148→Control Power-Loss
When Running.
HIGH DISCHARGE TEMP 149→Comp Discharge Temp
[VALUE] Exceeded Limit of
[LIMIT]*.
HIGH BEARING
150→Comp Thrust Brg Temp
TEMPERATURE
[VALUE] exceeded limit of
[LIMIT]*.
PRIMARY CAUSE
CCN has signaled the chiller to stop.This fault
must be manually reset from the default screen
of the ICVC.
LINE FREQUENCY in POWER screen must be
maintained between 45-52 Hz if LINE
FREQ=60Hz? is set to NO(50 Hz). LINE FRE-
QUENCY must be maintained between
55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
Check 2C AUX/HPR Gate Kill circuit.
COMPRESSOR 100% SPEED in VFD_CONF
screen must be set between 45-52 Hz if LINE
FREQ=60Hz? is set to NO(50 Hz). COMPRES-
SOR 100% SPEED must be set between
55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
VFD Gateway and VFD software versions are
not compatible.
Call Carrier Service.
VFD Gateway and ICVC software versions are
not compatible.
Call Carrier Service.
Check for high entering water temperature or
low condenser water flow.
Check current settings in VFD_CONF screen.
PRIMARY CAUSE
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.
Power loss has been detected in any phase.
Chiller automatically restarting.
A drop in line voltage has been detected within
2 voltage cycles.
Chiller automatically restarting if Auto Restart is
enabled in OPTIONS screen.
Check phase to phase and phase to ground line
power.
Check phase to phase and phase to ground line
power.
VFD Module has detected a hardware fault due
to electrical noise, power loss or software and
has reset. Chiller automatically restarting.
Check for power loss and sources of electro-
magnetic interference.
Check 24 vac control power supply to ICVC.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper condenser flow and
temperature.
Check for high lift or low load.
Check for fouled tubes or noncondensables in
the chiller.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil level and oil temperature.
92
ADDITIONAL CAUSE/REMEDY
ADDITIONAL CAUSE/REMEDY