Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 151

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

DESCRIPTION
Base Demand Limit
LCW Setpoint
ECW Setpoint
Ice Build Setpoint
Tower Fan High Setpoint
Upload all control configuration tables via service tool?
ICVC Software
Part Number (See ICVC Configuration Screen)
ICVC Controller Identification
VFD Gateway Version Number (See VFD_STAT Screen):
VFD Inverter Version Number (See VFD_STAT Screen):
VFD Rectifier Version Number (See VFD_STAT Screen):
19XRV PIC III SETPOINT TABLE CONFIGURATION SHEET
RANGE
40 to 100
10 to 120
(-12.2 to 48.9)
15 to 120
(-9.4 to 48.9)
15 to 60
(-9.4 to 15.6)
55 to 105
(13 to 41)
(See ICVC Configuration Screen)
UNITS
%
DEG F (C)
DEG F (C)
DEG F (C)
DEG F (C)
Yes
No
:
: BUS:
CL-3
DEFAULT
VALUE
100
50.0 (10)
60.0 (15.6)
40.0 (4.4)
75 (24)
ADDRESS:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents