Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 34

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

To access this display from the ICVC default screen:
1. Press
MENU
.
2. Press
.
SERVICE
3. Scroll down to highlight
VFD CONFIG DATA
4. Press
SELECT
.
5. Enter password (4444 Factory Default).
6. Scroll down to highlight
VFD_CONF
7. Press
SELECT
.
DESCRIPTION
Motor Nameplate Voltage
Compressor 100% Speed
Line Freq=60 Hz? (No=50)
* Rated Line Voltage
* Rated Line Amps
* Rated Line Kilowatts
* Motor Rated Load KW
* Motor Rated Load Amps
Motor Nameplate Amps
Motor Nameplate RPM
Motor Nameplate KW
Inverter PWM Frequency (0=4 k Hz, 1=2 k Hz)
Skip Frequency 1
Skip Frequency 2
Skip Frequency 3
Skip Frequency Band
Line Voltage % Imbalance
Line Volt Imbalance Time
Line Current % Imbalance
Line Current Imbal Time
Motor Current % Imbalance
Motor Current Imbal Time
Increase Ramp Time
Decrease Ramp Time
Single Cycle Dropout
NOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in other calculations and algorithms in the ICVC.
To access this display from the ICVC default screen:
1. Press
MENU
.
2. Press
.
SERVICE
3. Scroll down to highlight
EQUIPMENT SERVICE
4. Press
SELECT
.
5. Scroll down to highlight
OPTIONS
6. Press
SELECT
.
DESCRIPTION
Auto Restart Option
Remote Contacts Option
Soft Stop Amps Threshold
Surge / Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Min. Load Point (T1,P1)
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Full Load Point (T2,P2)
Surge/HGBP Delta T2
Surge/HGBP Delta P2
Surge/HGBP Deadband
Surge Protection
Surge Delta% Amps
Surge Time Period
Ice Build Control
Ice Build Option
Ice Build Termination
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle
Head Pressure Reference
Delta P at 0% (4mA)
Delta P at 100% (20mA)
Minimum Output
NOTE: No variables are available for CCN read or write operation.
Table 4 — ICVC Display Data (cont)
EXAMPLE 16 — VFD_CONF DISPLAY SCREEN
.
.
STATUS
346-480
45.0-62.0
0/1
346-480
10-1500
0-7200
0-7200
10-1500
10-1500
1500-3600
0-5600
0/1
0.0-102.0
0.0-102.0
0.0-102.0
0.0-102.0
1-10
1-10
5-40
1-10
5-40
1-10
5-60
5-60
0/1
EXAMPLE 17 — OPTIONS DISPLAY SCREEN
.
.
STATUS
0/1
DSABLE/ENABLE
0/1
DSABLE/ENABLE
40-100
%
0/1
0.5-20
^F
30-170
PSI
0.5-20
^F
50-170
PSI
0.5-3
^F
5-20
%
7-10
MIN
0/1
DSABLE/ENABLE
0-2
0/1
DSABLE/ENABLE
20-85
PSI
20-85
PSI
0-100
%
UNITS
VOLTS
Hz
NO/YES
VOLTS
AMPS
kW
kW
AMPS
AMPS
kW
Hz
Hz
Hz
Hz
%
SEC
%
SEC
%
SEC
SEC
SEC
DSABLE/ENABLE
UNITS
POINT
astart
modes
strtstop
srg_hgbp
hgb_dt1
hgb_dp1
hgb_dt2
hgb_dp2
hgb_db
surge_a
surge_t
ibopt
ibterm
ibrecyc
HPDPO
HPDP100
HPDPMIN%
34
POINT
DEFAULT
motor_nv
460
comp_100
60.0
line_frq
YES
vfd_volt
460
vfd_amps
200
vfd_rlkw
100
mot_rlkw
100
mot_rla
200
motorni
100
motorpm
3456
motorkw
100
pwm_freq
0
skipfrq1
102.0
skipfrq2
102.0
skipfrq3
102.0
skipband
0.0
v_unbal
10
v_time
10
lineim_i
40
lineim_t
10
motim_i
40
motim_t
10
ramp_inc
30
ramp_dec
30
cycdrop
DSABLE
DEFAULT
DSABLE
DSABLE
100
0
1.5
50
10
85
1
10
8
DSABLE
0
DSABLE
25
50
0