Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 155

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

DESCRIPTION
Comp Motor Temp Override
Cond Press Override
Rectifier Temp Override
Inverter Temp Override
Comp Discharge Alert
Comp Thrust Brg Alert
Chilled Medium
Chilled Water Deadband
Evap Refrig Trippoint
Refrig Override Delta T
Evap Approach Alert
Cond Approach Alert
Condenser Freeze Point
Flow Delta P Display
Evap Flow Delta P Cutout
Cond Flow Delta P Cutout
Water Flow Verify Time
Oil Press Verify Time
Recycle Control
Restart Delta T
Shutdown Delta T
Spare Alert/Alarm Enable
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
Spare Temp #1 Limit
Spare Temp #2 Enable
Spare Temp #2 Limit
NOTE: No variables are available for CCN read operation. Forcing shall not be supported on service screens.
19XRV PIC III SETUP1 TABLE CONFIGURATION SHEET
RANGE
150 to 200
(66 to 93)
90 to 165
(621 to 1138)
155 to 170
(68 to 77)
155 to 170
(68 to 77)
125 to 200
(52 to 93)
165 to 185
(74 to 85)
0/1
.5 to 2.0
(0.3 to 1.1)
0.0 to 40.0
(–17.8 to 4.4)
2.0 to 5.0
(1.1 to 2.8)
0.5 to 15
(0.3 to 8.3)
0.5 to 15
(0.3 to 8.3)
–20 to 35
(–28.9 to 1.7)
0 to 1
0.5 to 50.0
(3.4 to 344.8)
0.5 to 50.0
(3.4 to 344.8)
0.5 to 5
15 to 300
2.0 to 10.0
(1.1 to 5.6)
0.5 to 4.0
(0.3 to 2.2)
0 to 4
–40 to 245
(–40 to 118)
0 to 4
–40 to 245
(–40 to 118)
UNITS
°F (°C)
PSI (kPa)
°F (°C)
°F (°C)
°F (°C)
°F (°C)
WATER/
BRINE
ˆF (ˆC)
°F (°C)
ˆF (ˆC)
ˆF (ˆC)
ˆF (ˆC)
°F (°C)
DSABLE/
ENABLE
PSI (kPa)
PSI (kPa)
MIN
SEC
°F (°C)
°F (°C)
°F (°C)
°F (°C)
CL-7
DEFAULT
VALUE
200 (93)
125 (862)
160 (71)
160 (71)
200 (93)
175 (79)
WATER
1.0 (0.6)
33 (0.6)
3 (1.7)
5 (2.8)
6 (3.3)
34 (1.1)
DSABLE
5.0 (34.5)
5.0 (34.5)
5
40
5 (2.8)
1 (.0.6)
0
245 (118)
0
245 (118)