Carrier 19XRV Start-Up, Operation And Maintenance Instructions Manual page 153

Hermetic centrifugal liquid chillers with pic iii controls 50/60 hz hfc-134a
Table of Contents

Advertisement

DESCRIPTION
Motor Nameplate Voltage
Compressor 100% Speed
Line Freq=60 Hz? (No=50)
* Rated Line Voltage
* Rated Line Amps
* Rated Line Kilowatts
* Motor Rated Load KW
* Motor Rated Load Amps
Motor Nameplate Amps
Motor Nameplate RPM
Motor Nameplate KW
Inverter PWM Frequency
(0=4 k Hz, 1=2 k Hz)
Skip Frequency 1
Skip Frequency 2
Skip Frequency 3
Skip Frequency Band
Line Voltage % Imbalance
Line Volt Imbalance Time
Line Current % Imbalance
Line Current Imbal Time
Motor Current % Imbalance
Motor Current Imbal Time
Increase Ramp Time
Decrease Ramp Time
Single Cycle Dropout
NOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in other calculations and algorithms in the ICVC.
19XRV PIC III VFD_CONF TABLE CONFIGURATION SHEET
RANGE
380-460
45.0-62.0
0/1
346-480
10-1500
0-7200
0-7200
10-1500
10-1500
1500-3600
0-5600
0/1
0.0-102.0
0.0-102.0
0.0-102.0
0.0-102.0
1-10
1-10
5-40
1-10
5-40
1-10
5-60
5-60
0/1
UNITS
VOLTS
Hz
NO/YES
VOLTS
AMPS
kW
kW
AMPS
AMPS
kW
Hz
Hz
Hz
Hz
%
SEC
%
SEC
%
SEC
SEC
SEC
DSABLE/ENABLE
CL-5
DEFAULT
VALUE
460
60.0
YES
460
200
100
100
200
100
3456
100
0
102.0
102.0
102.0
0.0
10
10
40
10
40
10
30
30
DSABLE