Electrical Connections - Harsco Industrial 1004905923 Installation & Owner's Manual

Modu-fire forced draft gas-fired boiler
Table of Contents

Advertisement

3.3.3
Installation Clearances
If the boiler is to be installed near combustible surfaces, six (6") inches minimum clearance to the combustible
surface must be maintained.
Failure to provide for the service access clearances, even with non-combustible surfaces, may cause future
problems servicing the boiler.
The boiler must be installed in a space large in comparison to the boiler as described in the National Fuel Gas
Code, NFPA 54/ANSI Z223.1, Latest Edition.
C
C
A
A
Clearances from Adjacent Walls, Ceiling,
and Obstructions
Side Clearances for a Row of Boilers
Type of Surface
CSA Minimum Clearances to
Combustibles
Recommended Service
Clearances
B
B
Dimensions (inches)
A
B
C†
24
24*
24
30
24*
24
24**
boiler or row of boilers. Boilers may be installed immediately
adjacent to each other. However, Harsco Industrial,
Patterson-Kelley recommends this clearance between each
boiler when there is insufficient access at the rear to allow
for service and adjustment.
3.4
All field wiring connections for power and controls are in the
junction box on the back of the boiler. The boiler wiring label
is attached to the inside front door of the boiler. An external
electrical disconnect (not supplied with the boiler) with
adequate overload protection is required. The boiler must be
grounded in accordance with local codes or in the absence of
such requirements, in the U.S. with National Electrical
Codes, ANSI/NFPA No. 70 latest edition and in Canada, wire
according to the current Canadian Electrical Code.
Electrical
Connections
10
®
MODU-FIRE
Forced Draft Gas-Fired Boiler 2500-3000
D
† "C" dimension includes clearance to remove
the burner and installation of the air inlet duct.
Do not put pipes, other ducts, equipment, etc.
D
above the boiler.
24
* CSA minimum. Actual clearance depends upon
venting requirements.