External Static
Pressure
in. w.g.
Pa
.00
0
.05
10
.10
25
.15
35
.20
50
.25
60
.30
75
.40
100
.50
125
.60
150
.70
175
.75
185
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
External Static
Pressure
in. w.g.
Pa
.00
0
.05
10
.10
25
.15
35
.20
50
.25
60
.30
75
.40
100
.50
125
.60
150
.70
175
.75
185
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
506150−01 05/09
Table 8. CBX32M-042 Air Handler Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
cfm
L/s
Watts
1325
625
370
1335
630
370
1335
630
370
1330
630
365
1320
620
360
1300
615
355
1270
600
350
1195
565
330
1090
515
310
955
450
285
795
375
260
700
330
250
Table 9. CBX32M-048 Air Handler Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
cfm
L/s
Watts
1475
695
430
1480
700
430
1475
695
425
1465
690
420
1445
680
410
1415
670
405
1380
650
395
1290
610
370
1170
550
345
1020
480
320
840
395
295
740
350
280
Medium
cfm
L/s
Watts
1600
755
1585
750
1565
740
1540
725
1505
710
1470
695
1425
675
1320
625
1195
565
1050
495
875
415
780
370
Medium
cfm
L/s
Watts
1785
845
1770
835
1750
825
1720
810
1685
795
1645
775
1600
755
1485
700
1350
635
1190
560
1000
470
900
425
Page 16
High
cfm
L/s
455
1825
860
455
1790
845
450
1750
825
440
1710
805
435
1660
785
425
1610
760
415
1555
735
390
1430
675
365
1290
610
335
1135
535
310
965
455
295
875
415
High
cfm
L/s
520
1910
900
515
1895
895
510
1870
880
500
1840
865
490
1800
850
480
1755
830
465
1700
805
440
1580
745
410
1425
675
380
1250
590
350
1045
495
335
930
440
Watts
565
555
540
530
520
505
495
465
440
415
385
370
Watts
590
585
580
570
565
550
540
515
485
450
415