Sealing the Unit

WARNING
There must be an airtight seal between the bottom
of the air handler and the return air plenum. Use
fiberglass sealing strips, caulking, or equivalent
sealing method between the plenum and the air
handler cabinet to ensure a tight seal. Return air
must not be drawn from a room where this air
handler or any gas−fueled appliance (i.e., water
heater), or carbon monoxide−producing device (i.e.,
wood fireplace) is installed.
Seal the unit so that warm air is not allowed into the
cabinet. Warm air introduces moisture, which results in
water blow−off problems. This is especially important when
the unit is installed in an unconditioned area.
Make sure the liquid line and suction line entry points are
sealed with either the provided flexible elastomeric thermal
insulation, or field provided material (e.g. Armaflex,
Permagum or equivalent). Any of the previously mention
materials may be used to seal around the main and
auxiliary drains, and around open areas of electrical inlets.
Adjusting the Blower Speed Adjustments
MINIMUM BLOWER SPEEDS (WITH ELECTRIC
HEATERS)
For the minimum allowable speed for the CBX32M series
External Static
Pressure
in. w.g.
Pa
.00
0
.05
10
.10
25
.15
35
.20
50
.25
60
.30
75
.40
100
.50
125
.60
150
.70
175
.75
185
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
506150−01 05/09
Table 4. CBX32M-018/024 Air Handler Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
Low
cfm
L/s
Watts
700
330
245
695
330
245
690
325
240
680
320
235
665
315
230
650
310
220
635
300
215
590
280
205
535
255
190
470
220
175
395
185
165
350
165
155
units with electric heat, refer to the ECB29 installation
instructions.

AIR VOLUME ADJUSTMENT

Blower speed selection is accomplished by changing the
taps at the harness connector at the Blower motor as
illustrated in figure 17. Refer to unit wiring diagram in figure
15 on page 12. Refer to tables 4 through 11 for air handler
performance data.
PRESS THE TAB TO RELEASE WIRE CONNECTOR.
SELECT CONNECTOR LOCATION FOR NEW SPEED.
INSERT WIRE UNTIL IT CLICKS.
Figure 17. Blower Speed Tap Selection
Medium
cfm
L/s
Watts
895
425
890
420
875
415
860
405
845
400
825
390
800
380
745
355
685
320
605
285
520
245
475
225
Page 14
CONNECTOR
High
cfm
L/s
300
1030
485
295
1015
480
290
1000
470
285
980
465
280
960
455
275
935
440
265
910
430
250
850
400
235
780
370
220
705
330
200
615
290
195
565
265
HARNESS
Watts
365
360
355
345
340
335
325
310
295
280
265
255