Daikin EHYHBH05AA Installation Manual page 15

Altherma hybrid heat pump – heat pump module
Hide thumbs Also See for EHYHBH05AA:
Table of Contents

Advertisement

Space heating/cooling control
Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1 
dependent
▪ 2  (Fixed/scheduled):  Absolute  +
scheduled  (only  for  leaving  water
temperature control)
▪ 3 
dependent  +  scheduled  (only  for
leaving water temperature control)
[A.3.1.1.3]
[1­00]
Weather­dependent curve (heating):
T t
[1­01]
[1­02]
[1-02]
[1­03]
[1-03]
▪ T
(main)
▪ T
[A.3.1.1.4]
[1­06]
Only for EHYHBX08. Weather­
dependent curve (cooling):
[1­07]
T t
[1­08]
[1­09]
[1-08]
[1-09]
▪ T
(main)
▪ T
INFORMATION
In order  to optimise  comfort as well  as running  costs, it is
recommended  to  choose  weather­dependent  setpoint
operation.  Set  the  settings  carefully;  they  have  significant
influence  on  heat  pump  as  well  as  boiler  operation.  Too
high leaving water temperature can result in constant boiler
operation.
Leaving water temperature: Additional zone
#
Code
[A.3.1.2.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1 
dependent
▪ 2  (Fixed/scheduled):  Absolute  +
scheduled  (only  for  leaving  water
temperature control)
▪ 3 
dependent  +  scheduled  (only  for
leaving water temperature control)
EHYHBH05AAV3 + EHYHBH/X08AAV3
Daikin Altherma hybrid heat pump – heat pump module
4P349587­1C – 2013.10
Description
(Weather 
dep.): 
Weather­
(WD/scheduled): 
Weather­
[1-00]
[1-01]
:  Target  leaving  water  temperature
t
: Outdoor temperature
a
[1-06]
[1-07]
:  Target  leaving  water  temperature
t
: Outdoor temperature
a
Description
(Weather 
dep.): 
Weather­
(WD/scheduled): 
Weather­
#
Code
[A.3.1.2.3]
[0­00]
[0­01]
[0­02]
[0­03]
[A.3.1.2.4]
[0­04]
[0­05]
[0­06]
[0­07]
T a
Pump control: Flow target
#
Code
N/A
[8­0B]
N/A
[8­0C]
N/A
[8­0D]
INFORMATION
T a
Changing  these  settings  can  result  in  discomfort.  Refer  to
the installer reference guide for more information.
Leaving water temperature: Modulation
#
Code
[A.3.1.1.5]
[8­05]
5 Configuration
Description
Weather­dependent curve (heating):
T t
[0-01]
[0-00]
[0-03]
[0-02]
▪ T
:  Target  leaving  water  temperature
t
(additional)
▪ T
: Outdoor temperature
a
Only for EHYHBX08. Weather­
dependent curve (cooling):
T t
[0-05]
[0-04]
[0-07]
[0-06]
▪ T
:  Target  leaving  water  temperature
t
(additional)
▪ T
: Outdoor temperature
a
Description
Target flow rate during heat pump
operation.
Target flow rate during hybrid
operation.
Target flow rate during boiler operation.
Description
Leaving water temperature modulation:
▪ 0 (No): Disabled
▪ 1  (Yes):  Enabled.  The  leaving  water
temperature  is  calculated  according
to  the  difference  between  desired
and  actual  room  temperature.  This
allows  better  matching  of  the
heat  pump  capacity  to  actual
required  capacity  and  results  in  less
start/stop  cycles  of  the  heat  pump
and more economic operation.
Installation manual
T a
T a
15