Space heating/cooling control
Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
dependent + scheduled (only for
leaving water temperature control)
[A.3.1.1.3]
[100]
Weatherdependent curve (heating):
T t
[101]
[102]
[1-02]
[103]
[1-03]
▪ T
(main)
▪ T
[A.3.1.1.4]
[106]
Only for EHYHBX08. Weather
dependent curve (cooling):
[107]
T t
[108]
[109]
[1-08]
[1-09]
▪ T
(main)
▪ T
INFORMATION
In order to optimise comfort as well as running costs, it is
recommended to choose weatherdependent setpoint
operation. Set the settings carefully; they have significant
influence on heat pump as well as boiler operation. Too
high leaving water temperature can result in constant boiler
operation.
Leaving water temperature: Additional zone
#
Code
[A.3.1.2.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
▪ 3
dependent + scheduled (only for
leaving water temperature control)
EHYHBH05AAV3 + EHYHBH/X08AAV3
Daikin Altherma hybrid heat pump – heat pump module
4P3495871C – 2013.10
Description
(Weather
dep.):
Weather
(WD/scheduled):
Weather
[1-00]
[1-01]
: Target leaving water temperature
t
: Outdoor temperature
a
[1-06]
[1-07]
: Target leaving water temperature
t
: Outdoor temperature
a
Description
(Weather
dep.):
Weather
(WD/scheduled):
Weather
#
Code
[A.3.1.2.3]
[000]
[001]
[002]
[003]
[A.3.1.2.4]
[004]
[005]
[006]
[007]
T a
Pump control: Flow target
#
Code
N/A
[80B]
N/A
[80C]
N/A
[80D]
INFORMATION
T a
Changing these settings can result in discomfort. Refer to
the installer reference guide for more information.
Leaving water temperature: Modulation
#
Code
[A.3.1.1.5]
[805]
5 Configuration
Description
Weatherdependent curve (heating):
T t
[0-01]
[0-00]
[0-03]
[0-02]
▪ T
: Target leaving water temperature
t
(additional)
▪ T
: Outdoor temperature
a
Only for EHYHBX08. Weather
dependent curve (cooling):
T t
[0-05]
[0-04]
[0-07]
[0-06]
▪ T
: Target leaving water temperature
t
(additional)
▪ T
: Outdoor temperature
a
Description
Target flow rate during heat pump
operation.
Target flow rate during hybrid
operation.
Target flow rate during boiler operation.
Description
Leaving water temperature modulation:
▪ 0 (No): Disabled
▪ 1 (Yes): Enabled. The leaving water
temperature is calculated according
to the difference between desired
and actual room temperature. This
allows better matching of the
heat pump capacity to actual
required capacity and results in less
start/stop cycles of the heat pump
and more economic operation.
Installation manual
T a
T a