Temperature; Humidity - HP StorageWorks XP12000 Site Preparation Manual

Disk array
Hide thumbs Also See for StorageWorks XP12000:
Table of Contents

Advertisement

Temperature

Humidity

Site Requirements
Table 13. Temperature specifications
Temperature range type
Recommended operating temperature range
Operating temperature
Nonoperating temperature range
Shipping and storage temperature
(product packed in factory packing)
Temperature shock immunity
(maximum rate of temperature change)
Over-temperature warning
Over-temperature shutdown
Maintain proper humidity levels. High humidity levels cause galvanic
actions to occur between some dissimilar metals. This eventually causes a
high resistance between connections, leading to equipment failure.
Low humidity contributes to undesirably high levels of electrostatic
charges. This increases the electrostatic discharge (ESD) voltage potential.
ESD can cause component damage during servicing operations.
Low humidity levels are often the result of the facility heating system and
occur during the cold season. Most heating systems provide air with a low
humidity level, unless the system has a built-in humidifier.
Range
21° to 24°C
70° to 75°F
16° to 32°C
61° to 89°F
–10° to +43°C
14° to 109°F
–25° to +60°C
–13° to +140°F
10°C per hour
18°F per hour
At 40°C
At 104°F
At 60°C
At 140°F
47