Operating specifications
This section provides some general specifications. For complete specifications, see
the system site preparation guide, available on the HP XP Disk Array web site:
http://h18006.www1.hp.com/storage/xparrays.html.
Temperature
Temperature range type
Recommended operating temperature
range
Operating temperature
Nonoperating temperature range
Shipping and storage temperature
(product packed in factory packing)
Temperature shock immunity (maximum
rate of temperature change)
Over-temperature warning
Over-temperature shutdown
32
Hardware
Range
21 to 24 degrees C, 70 to 75 degrees F
16 to 32 degrees C, 61 to 89 degrees F
–10 to +43 degrees C, 14 to 109 degrees F
–25 to +60 degrees C, –13 to +140 degrees F
10 degrees C per hour, 18 degrees F per hour
At 40 degrees C, 104 degrees F
At 60 degrees C, 140 degrees F