30-amp, single-phase DKU
Table 27. 30-amp, 50 or 60 Hz, single-phase DKU operation
Parameter
Minimum operating voltage (Vac)
Maximum operating voltage (Vac)
Rated line current per power cord (Arms)
Number of power cords
Recommended circuit breakers
Number of circuit breakers
Dropout carry-through time at minimum line voltage (ms)
1 60 Hz only.
2 Units with only two power cords require only two circuit breakers.
30-amp, three-phase DKU
Table 28. 30-amp, 50 or 60 Hz, three-phase DKU operation
Parameter
Minimum operating voltage (Vac)
Maximum operating voltage (Vac)
Rated line current per power cord (Arms)
Number of power cords
Recommended circuit breakers
Number of circuit breakers
Dropout carry-through time at minimum line
voltage (ms)
1 60 Hz only.
72
2
10.4 10.0
30A 30A 30A 30A 30A 30A 30A 30A
HP StorageWorks XP12000 Disk Array Site Preparation Guide
Nominal rated voltage (Vac)
200
184
212
9
4
30A
4
60
Nominal rated voltage (Vac)
1
200 208
220
184
191
202
212
220
233
9.4
2
2
2
2
2
2
60
60
60
1
208
220
230
191
202
212
220
233
244
8.7
8.2
7.8
4
4
30A
30A
30A
4
4
60
60
230
240
380
212
221
350
244
254
403
9.0
8.7
5.5
2
2
2
2
2
2
60
60
60
240
221
254
7.5
4
4
30A
4
4
60
60
400
415
368
382
424
440
5.2
5.0
2
2
2
2
60
60