6.23 Check code Trouble shooting CH61, CH62
Display
Title
code
Condenser
61
pipe sensor
temp. high
Heat sink sensor
62
temp. high
Check Flow Chart
Check Over load condition
- Refrigerant leakage
- Condenser is blocked
- Outdoor fan is locked
Yes
Unplug the sensor
on Outdoor unit PCB
Check the
Connector connection
Is it normal ?
Yes
Estimate the resistance
of each sensor.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• condenser pipe
sensordetected high
temp.(65˚C)
• heat sink sensor
detected high temp.
(85˚C)
No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
No
Correct connection
- 85 -
Check point & Normal condition
• Check the load condition.
• Check the sensor of Condenser pipe sensor.
• Normal resistor : 5KΩ/ at 25˚C (Unplugged)
• Normal voltage : 2.5Vdc / at 25˚C (Plugged)
• Check the load condition.
• Check the sensor of heat sink.
• Normal resistor : 10KΩ/ at 25˚C (Unplugged)
• Normal voltage : 2.5Vdc / at 25˚C (Plugged)
Is the resistance of
the Sensor is 5kΩ
/10kΩ at 25˚C?
Yes
Plug the sensor
on Indoor unit PCB
Estimate the Voltage
of each sensor.
Yes
Is the voltage of the
sensor is 4.5Vdc /
2.5Vdc at 25˚C
Yes
Repair or Change the PCB.
5. Trouble Shooting
No
Change the sensor
No
Change the sensor
LGE Internal Use Only