Wired Remote Controller Installation - Sanyo 26 series Installation Instructions Manual

Split system heat pump air conditioner
Table of Contents

Advertisement

6-2. Wired Remote Controller Installation

G
Do not supply power to the unit or try
WARNING
to operate it until the tubing and wiring
to the outdoor unit are completed.
G
Do not twist the control wiring with the
CAUTION
power wiring or run it in the same
metal conduit, because this may cause
malfunction.
G
Install the remote controller away from
sources of electrical noise.
G
Install a noise filter or take other
appropriate action if electrical noise
affects the power supply circuit of the
unit.
G
If local electrical codes allow, this
remote controller can be mounted
using a conventional wall box for flush
mounting.
(1) When you open the decorative cover, you will see
two gaps under the remote controller. Insert a coin
into these gaps and pry off the back case.
(Fig. 6-4)
(2) Attach the back case with the 2 small screws
provided. Using a screwdriver, push open the cut-
outs on the back case. These holes are for screws.
Use the spacers and take care not to tighten the
screws excessively. If the back case will not seat
well, cut the spacers to a suitable thickness.
(Fig. 6-3)
(3) Connect the remote controller wiring (2 wires) cor-
rectly to the corresponding terminals in the
electrical component box of the indoor unit.
When wiring, do not connect
the remote controller wires to
CAUTION
the adjacent terminal block for
the power wiring. Otherwise,
the unit will break down.
(4) To finish, fit the back tabs of the case into the
remote controller and mount it.
M4 × 25
Screws (2)
Wired remote
controller
Decorative
cover
Control panel
Gap
Coin
61
Concealed box for 1
Spacer
Under case
(Back case)
Fig. 6-3
Gap
Fig. 6-4
RC
(WD)