compatible with BIS Security Engine
v2.1.1271 or later. This addresses the issues
described in the BIS SEE and GV2/G Series
Technical Service Note (P/N: F01U073249).
Changes made allow the Relay Latches on
point fault option for the
Type
feature to reset when a passcode is
entered even when the associated point has
not returned to normal. This correction does
not apply to invisible points.
Corrections made to the View Points menu in
the D1260 and D1260B user interface now
allow the display to advance even when there
is only one viewable point in the area. This
addresses the issue described in the
Unresponsive D1260 Keypad Technical Bulletin
(P/N: TBI 02-09-07 01).
Corrections made to the Door Control
(COMMAND 46) menu and its associated sub-
menus now enforce the door's area
assignment and the user authority level
assignments for the following permissions:
L# Unlock Door
L# Cycle Door
,
Secure Door
.
Corrections made now allow the use of any
enhanced communication path in any route
group. For example, Enhanced
Communication Path 2 can be the primary
destination for Route Group 4 with Phone
Number 3 as backup. However, the primary
and backup paths for any route group must
be different.
Changes made now allow the clearing of the
alarm memory when there are only non-fire
points faulted. However, the UL required
prevention of alarm memory erasure while
there are fire points faulted is still enforced.
If an area has faulted fire and non-fire points,
then the alarm memory is locked until the fire
points are returned to normal.
Changes made to the enhanced
communication path acknowledgement wait
time do not allow the no-ack-required option
when anti-replay is enabled for the same
Path # Anti-Replay
path. When
Path # ACK Wait Time
and
the zero value is treated as if it were the
minimum setting of 5 seconds by the control
panel.
© 2013 Bosch Security Systems, Inc.
P## Relay Response
L#
, and
is set to Yes
with is set to 0,
D9412GV2/D7412GV2 Release Notes for Version 7.09
D9412GV2/D7412GV2
Changes made allow the Manual Idle Text
Forward Scroll to show faulted points when
CC# Scroll Lock
you set
condition occurs.
Changes made allow the View Area Status
display on the D1260 and D1260B Keypads to
show the default Area Arm Status text.
Changes made to the View Log menu on the
D1260 and D1260B Keypads now show the
second line of event information.
Changes prohibit using a walk test command
when the control panel is in Power-up
Standby mode. During the Power-up Standby
mode, all points on the control panel are
initializing and considered to be in the off-
normal state. The system ignores any state
transitions until the Power-up Standby
window expires. Because of required SIA CP-
01 enhancements to the Fire Walk Test
command initiated in v7.05, any 24-hour or
fire point that remains off-normal when you
exit from the test is automatically bypassed
regardless of the point's configuration. In the
GV2 control panels, any bypassed non-
controlled point (fire or 24-hour) can be
returned to service only by individually
unbypassing each point using CMD 00. These
changes address the issues described in the
GV2 Fire Walk Test Technical Bulletin (P/N: TBI
09-27-07 01).
Changes made to the Trouble LED on the
D1255RB and D1256RB Fire Keypads, and
D1257RB Fire Annunciator, now indicate
when the control panel is in Power-Up
Standby mode.
Changes made improve the accuracy of the
Low Battery Monitor.
2.3.1
New Features in Version 7.07
Enhanced Communication Path Port
Numbers: A new prompt was added to each
of the four enhanced communication paths
(Path # Port Num) to specify an individual
destination port number. All four IP/port
pairs must be unique to ensure event
acknowledgements are accounted for
correctly. Duplicate IP address/port pairs can
cause unreliable communication. This
enhancement further facilitates the Port
Address Translation feature added in V7.06.
When upgrading from V7.06 or later, these
Page 5
to Yes and an alarm
F01U003637-06