Standard Series H Area Register Mapping
Register
T#
Address
49000 
1
49001
2
49002
3
49003
5
49004
4
49005
45
49006
46
49007
49
49008
50
49009
51
49010
39
49011
40
49012
41
Note:

To use register 49000, you must jumper terminals J1–8, J1–9,
J1–10 and J1–17 together to allow the motor to run.
Read/Write
Read/Write
Run Cmd (0=stop, 1=fwd, 2=rev, 3=bipolar)
Write Only
Run Inhibit (1=stop, regardless of Control
Source)
Read/Write
Control Source (0=keypad,1=terminal
strip,2=network)
Read/Write
Command Mode (see NOTE 2)
Read Only
Control State (0=not ready, 1=ready, 2=enabled,
3=stopping, 4=faulted
Read Only
Fault Status (0=no fault present)
Write Only
Fault Reset (1=execute fault reset)
Write Only
Force Fault (0–1=force network fault)
Read Only
Security Status (0=disabled, 1=unlocked,
2=locked)
Write Only
Security Lock (valid code unlocks, any other
locks)
Read/Write
Table Select (parameter table select 0–3)
Read/Write
Acc/Dec Group (1–2)
Read/Write
Watchdog Time (0=disable) (10 ms minimum
for vector) (1 sec. minimum for inverter)
(see NOTE 3)
Continued
Description