Baldor Modbus Plus Installation And Operating Manual page 32

Table of Contents

Advertisement

H Series – Fault Message Description
Fault Message
Line Regen
Feedback Fault
Invalid Base ID
Low INIT Bus V
Regen Res
Power
Current SENS
FLT
HW
Desaturation
HW Ground
Fault
Resolver Fault
HW Power
Supply
Overcurrent
Bus
Overvoltage
Following ERR
Torque Prove
Bus
Undervoltage
3 Sec Overload
Over Speed
Motor Temp
Heatsink Temp
External Trip
Param
Checksum
Fault Code
15H
18H
1
1
Fault in Line REGEN converter unit -
Series 21H Line REGEN Inverter control.
2
Loss of encoder feedback.
3
3
Failed to read configuration from the Power
Base ID value in software.
4
4
Low bus voltage detected on start–up.
5
5
Excessive power dissipation required by
Dynamic Brake Hardware.
6
6
Failure to sense phase current.
7
7
High output current condition detected (greater
than 400% of rated output current).
8
8
Ground Fault detected (output current leakage
to ground).
9
Loss of resolver feedback.
10
10
Control Board power supply failure detected.
11
11
Continuous current limit exceeded.
12
12
High DC Bus voltage.
13
Motor speed/position does not follow command.
14
Unbalanced current between all 3 phases.
15
15
Low DC Bus voltage condition detected.
16
16
Peak output current exceeded the 3 second
rating value.
17
Motor RPM exceeded 110% of MAX Speed.
18
Motor over temperature
19
19
Control heatsink exceeded temperature limit.
18
20
Connection at J1/J4 pin 16 and 17 is open.
51
21
Parameter checksum error.
Fault Description
Software Setup 5-11

Advertisement

Table of Contents
loading

Table of Contents