Baldor Modbus Plus Installation And Operating Manual page 25

Table of Contents

Advertisement

For 15Hand 21H Inverter controls, use the following registers for
communication. For all other H controls, use the Standard Series H
Area Register Mapping.
Series 15H Specific Area Register Mapping
Register
T#
Address
47000
31
47001
45
47002
17
47003
18
47004
19
47005
33
47006
34
47007
35
47008 
1
47009
5
47010
6
47011
3
47012
47013
75
47014
46
Notes:
After the fault is cleared (1=execute fault reset), you must send a
stop (run cmd=0) followed by the direction for the run command
again. Otherwise, the motor will not run.

To use register 47008, you must jumper terminals J4–8, J4–9,
J4–10 and J4–17 together to allow the motor to run.
5-4 Software Setup
Read/Write
Read Only
Terminal Strip (see NOTE 1)
Read Only
Fault Status (0=no fault present)
Read Only
Current Actual (100mA RMS)
Read Only
Speed Actual (RPM)
Read Only
Frequency Actual (.1 Hz)
Read Only
Software Revision (ex S15–4.03 is returned as 403)
Read Only
Product Series (ex Series 15H returns 15)
Read Only
Product Class (5=H)
Read/Write
Run Cmd (0=stop, 1=fwd, 2=rev, 3=bipolar)
Read/Write
Command Mode (see NOTE 2)
Read/Write
Hz Speed Ref
Read/Write
Control Source (0=keypad, 1=terminal strip, 2=net-
work)
Reserved
Write Only
Digital Output
Write Only
Fault Reset (1=execute fault reset)
Description