Advertisement

Guide specifications (cont)
b. Display menus shall provide clear language
descriptions of all menu items, operating
modes, configuration points and alarm
diagnostics. Reference to factory codes shall
not be accepted.
c. RJ-14 connection plug shall allow display
module to be connected to factory-installed
receptacle.
d. Industrial grade coiled extension cord shall
allow the display module to be moved
around the chiller.
e. Magnets shall hold the display module to
any sheet metal panel to allow hands-free
operation.
f. Display module shall have NEMA 4x
housing
suitable
environments.
g. Display shall have back light and contrast
adjustment for easy viewing in bright
sunlight or night conditions.
h. Raised surface buttons with positive tactile
response.
15. Touch Pilot™ Display:
Unit shall be supplied with a remote mount
touch screen display for network attachment to
the chiller.
16. GFI Convenience Outlet:
Shall be factory or field installed to provide the
chiller with a 4 amp GFI receptacle. The recep-
tacle shall have independent fuse protection.
The convenience outlet is a 115-v female
receptacle.
17. Freeze Protection Cooler Heaters:
Cooler heaters shall provide protection from
cooler freeze-up to –20 F (–29 C).
18. Value Sound Fans:
Shall provide propeller-type fans for applica-
tions that are not highly sound-sensitive.
58
for
use
in
outdoor
19. Ultra-Low Sound:
Shall provide an acoustic enclosure around
each compressor in conjunction with low-sound
aero-acoustic fans to provide significant chiller
sound reduction.
20. High SCCR (Short Circuit Current Rating):
The optional high SCCR (short circuit current
rating) device shall allow the chiller to tolerate a
65 kA (208/230, 380 and 460-v units) or
25 kA (575-v units) short circuit current for a
brief period of time while protecting down-
stream components. The high SCCR option
shall provide a higher level of protection than
the standard unit.
21. Digital Compressor Option:
Shall provide a factory-installed digital compres-
sor to provide incremental steps for tighter tem-
perature control (not available on size 018
units).
22. Remote Cooler Kit:
Field-installed remote cooler kit shall provide
the additional hardware required to remotely
mount the cooler from the unit. There are limits
to total separation of the unit to the cooler as
well as vertical separation limits, and these shall
be delineated in the accessory installation
instructions. Never bury refrigerant piping on
these or any other applications.
23. Wind Baffles:
Wind baffles facilitate operation down to
–20 F (–29 C) when used in conjunction with
low
ambient
temperature
control.
24. Low Sound Compressor Blankets:
Accessory low sound compressor blankets shall
reduce unit sound levels by providing an acous-
tic blanket on each compressor.
head
pressure