Controls and Indicators

1-6
The only external control is the SERVICE pushbutton. The LEDs on the front of the LBIM
indicate its operating status.
Table 1-3. LBIM Controls and Indicators
Switch
Type
SERVICE
Momentary contact
pushbutton
Indicator
State
PWR
Lighted
OUT MSG
Flashes briefly
Lighted briefly
Flashes alternately
with IN MSG LED
Flashes together with
IN MSG LED
IN MSG
Flashes briefly
Lighted briefly
Flashes alternately
with OUT MSG LED
Flashes together with
OUT MSG LED
SVC
Not lighted
Flashing
Lighted
Series 90™-30 PLC LONWORKS® Bus Interface Module User's Manual – June 1997
Function
When pressed, the LBIM's Neuron chip broadcasts its unique 48-
bit Neuron identification code and program identifier to the
L
W
network. This function is used to facilitate
ON
ORKS
installation of the LBIM in the L
Meaning
(Power) +5 VDC primary power is present at the LBIM's logic
circuitry.
(Outbound Message) An update message for a bound network
variable is sent by the LBIM to the L
Powerup sequence in process.
The configuration parameter value file or the network variable
bindings are being saved into the flash memory.
A powerup error has occurred. For troubleshooting information,
refer to Chapter 5.
L
W
wink function implemented. See "Wink Function" in
ON
ORKS
Chapter 5.
(Inbound Message) Flashes briefly (10ms) when an update
message for a bound network variable is received by the LBIM
from the L
W
network.
ON
ORKS
Also lighted briefly during powerup sequence.
Powerup sequence in process.
The network variable configuration is being saved into the flash
memory.
A powerup error has occurred. For troubleshooting information,
refer to Chapter 5.
L
W
wink function implemented. See "Wink Function" in
ON
ORKS
Chapter 5.
Normal operation.
(Service) The LBIM is in a L
LBIM network variables and PLC mapping are configured and it
is waiting for configuration from a network management tool.)
When SERVICE button is pressed.
W
network.
ON
ORKS
W
network.
ON
ORKS
W
unconfigured state. (The
ON
ORKS
GFK-1322A