Engineering; Connection Terminals; Connection Diagrams; Water-Based Fan Coil Applications With Rdf300 - Siemens RDF300 Documentation

Semi-flush-mounted room temperature controllers for fancoils, with lcd
Hide thumbs Also See for RDF300:
Table of Contents

Advertisement

RDF300.../RDF400...
RDF340...
Application:
2-pipe fan coil units
Application:
2-pipe fan coil units
with electrical heater
Siemens
Building Technologies
6

Engineering

6.1

Connection terminals

L
X1 M
X2
Q1 Q2 Q3
Y11 N Y21
N
G
X1
M
X2
L
Q1 Q2 Q3 Y10 G0
G0
6.2

Connection diagrams

6.2.1
Water-based fan coil applications with
RDF300.../RDF400...
L
S1
S2
10 A
B1
B2
X2
L
X1
M
Q1 Q2 Q3
N
Y11
I
II III
M1 Y1
5(2)A
5(2)A
max.
N
max.
L
S1
S2
10 A
B1
B2
L
X1
M
X2
N
Q1 Q2 Q3
Y11
I
II III
M1 Y1
5(2)A
5(2)A
max.
N
max.
RDF300.../RDF340.../RDF400... Basic Documentation
6BEngineering
L, N
Operating voltage AC 230 V
Q1
Control output "Fan speed 1 AC 230 V"
Q2
Control output "Fan speed 2 AC 230 V"
Q3
Control output "Fan speed 3 AC 230 V"
Y11,Y21
Control output "Valve" AC 230 V (N.O., for
normally closed valves), output for
compressor or output for electrical heater
X1, X2
Multifunctional input for temperature
sensor (e.g. QAH11.1) or potential-free
switch
M
Measuring neutral for sensor and switch
G, G0
Operating voltage controller AC 24 V
SELV
L
Operating voltage for fan AC 230 V
Q1
Control output "Fan speed 1 AC 230 V"
Y20
Q2
Control output "Fan speed 2 AC 230 V"
Q3
Control output "Fan speed 3 AC 230 V"
Y10,Y20
Control output for 0...10 V actuator
X1, X2
Multifunctional input for temperature
sensor (e.g. QAH11.1) or switch
M
Measuring neutral for sensor and switch
M1
3-speed fan
N1
Room temperature controller
RDF300.../RDF400...
Y1
Zone valve
S1, S2 Switch (keycard, window contact, etc.)
B1, B2 Temperature sensor (return air temperature,
Y21
external room temperature, changeover
N1
sensor, etc.)
M1
3-speed fan
N1
Room temperature controller
RDF300.../RDF400...
Y1
Zone valve
E1
Electrical heater
S1, S2 Switch (keycard, window contact, etc.)
Y21
N1
B1, B2 Temperature sensor (return air temperature,
external room temperature, changeover
sensor, etc.)
E1
5(2)A
max.
31 / 40
CE1P3076en
28 Aug 2008

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdf340Rdf400Rdf300.02Rdf400.01

Table of Contents