Siemens RDF300 Documentation page 28

Semi-flush-mounted room temperature controllers for fancoils, with lcd
Hide thumbs Also See for RDF300:
Table of Contents

Advertisement

#
Parameter
Expert Level
P30
P-band/Switching differential for heating mode
P31
P-band/Switching differential for cooling mode
P33
Dead zone in Comfort mode
P34
Setpoint differential
P35
Integral time
P36
Heating/cooling changeover switching point for cooling
P37
Heating/cooling changeover switching point for heating
P38
X1 functionality
P39
Operating action for X1 if digital input
P40
X2 functionality
P41
Operating action for X2 if digital input
P44
Runtime for 3-position output (Y11/Y21)
P48
Minimum output on-time via on/off control output
P49
Minimum output off-time via on/off control output
P50
Purge function (minimum every 2 hours)
P51
Floor heating limit temperature
P52
Fan operation
P53
Fan speed
P54
Fan overrun time (only when electric heater is used)
P55
Switching point fan speed high
P56
Switching point fan speed med
P57
Switching point fan speed low
P58
Fan start kick
P59
Fan minimum on-time
P60
Fan kick in Comfort mode (time to next kick)
P61
Fan kick in Energy Saving mode (time to next kick)
P62
Clean filter reminder runtime
P65
Heating setpoint for Standby
P66
Cooling setpoint for Standby
P69
Temporary setpoint for Comfort mode
P70
Infrared receiver
P71
Parameter reset
Set value to ON and confirm by pressing the + and – buttons
Diagnostic & Test
d01
Application
d02
Status input X1
d03
Status input X2
d05
Test mode to check the 3-position Y11/Y21 actuator direction.
Note that this parameter can be quit only if the setting is back
at "---" and by pressing + and – buttons
28 / 40
Siemens
Building Technologies
(Wheat
)
Stb
(Wcool
)
Stb
RDF300.../RDF340.../RDF400... Basic Documentation
4BFunctions
Factory
Setting range
setting
2K
0.5 ... 6 K
1 K
0.5 ... 6 K
2 K
0.5 ... 5 K
2 K
0.5 ... 5 K
5 min
0...10 min
16 °C
10...25 °C
28 °C
27...40 °C
3 (Op mode
0:= NA
switchover)
1:= Ext/Return air temp
2:= Heat/cool changeover
3:= Operating mode switch
4:= Dewpoint monitor
5:= Enable electrical heater
6:= Alarm input
0 (N.O.)
0:= Normally open
1:= Normally closed
2 (H/C c/o)
Same as P38
0 (N.O.)
0:= Normally open
1:= Normally closed
150 s
50...240 sec
1 min.
1...20 minutes
1 min.
1...20 minutes
OFF
OFF: Inactive
1...5 min
OFF
OFF, 10..50 °C
1 (Enabled)
0:= Disabled
1:= Enabled
2:= Only in heating
3:= Only in cooling
2 (3-speed)
1:= 1-speed
2:= 3-speed
60 sec
0 ... 300 sec
100%
80..100%
65%
30..75%
10%
1..15%%
ON
ON: enabled
OFF: disabled
2 min
1 ... 5 min
0 (continuous)
0...89min, OFF
OFF
0...359min, OFF
OFF
OFF, 100 ... 9900 hours
8 °C
OFF, 5 °C...Wcool
OFF
OFF, Wheat
OFF
OFF:= Disabled
ON := Enable
OFF
OFF:= Disabled
ON := Enable
OFF
OFF:= Idle
ON: = Reset
Diagnose
2P:=
2-pipe
2PEL:= 2-pipe & el. heater
4P:=
4-pipe
2P3P:= 2-pipe 3pos
Diagnose
0:= Digital input
not activated
1:= Digital input activated
0...49 °C = measured
00 := H/C input short
100:= H/C input open
Diagnose
Same as d02
Diagnose
"---" := no signal
OPE:= Y11 active
CLO:= Y21 active
Stb
...40 °C
Stb
temp. value
open
close
CE1P3076en
28 Aug 2008