Siemens RDF300 Documentation page 27

Semi-flush-mounted room temperature controllers for fancoils, with lcd
Hide thumbs Also See for RDF300:
Table of Contents

Advertisement

Control parameters
#
Parameter
Service Level
P01
Control sequence
P02
Mode selection via user operating mode button
P04
Selection of °C or °F
P05
Sensor calibration
P06
Standard temperature display
P07
Additional user info
P08
Comfort basic setpoint
P09
Minimum setpoint limitation for Comfort (WminComf)
P10
Maximum setpoint limitation for Comfort (WmaxComf)
P11
Heating setpoint for Energy Saving
P12
Cooling setpoint for Energy Saving
P13
Electrical reheater for cooling mode
P14
Keypad lock
(Press the operating mode button
or disable the keypad lock)
Note
Siemens
Building Technologies
(WheatEco)
(WcoolEco)
for 7 seconds to enable
• P02 is not available when the controller is commissioned for manual
heating/cooling changeover P01=2
• Parameter display depends on selected application and function
(x) Not available
RDF300.../RDF340.../RDF400... Basic Documentation
4BFunctions
Factory
Setting range
setting
2-pipe:
[0..3]
0:= Heating only
1 (Cool only)
1:= Cooling only
4-pipe:
2:= Manual H/C
[2...4]
3:= Auto changeover
4 (Heat&Cool)
4:= Heating & cooling
1 (Stb, Comf)
1 = Stb,Comf
2 = Stb, Comf, Eco
°C
(0) °C or
(1) °F
0.0 K
– 3 ... +3 K
0 (Room temp)
0:= Room temperature
1:= Setpoint
0 (no display)
0:= no display
1:= Temp in °C and °F
21 °C
5 ... 40 °C
5 °C
5 ... 40 °C
35 °C
5 ... 40 °C
15 °C
OFF, 5 °C...WcoolEco
30 °C
OFF, WheatEco...40 °C
ON
ON:= enabled
OFF:= disabled
0 (Unlocked)
0:= Unlocked
1:= Auto lock
2:= Manual lock
27 / 40
CE1P3076en
28 Aug 2008