Additional Features - Siemens RDF300 Documentation

Semi-flush-mounted room temperature controllers for fancoils, with lcd
Hide thumbs Also See for RDF300:
Table of Contents

Advertisement

Water-based fan coil
application
Compressor-based
application
Universal applications
Automatic H/C
changeover
Remote heating/
cooling changeover
External / return air
temperature sensor
12 / 40
Siemens
Building Technologies
Use with one or two valves for heating and cooling, heating/cooling with
changeover, heating only, or cooling only.
Use with one 1-stage compressor for heating and cooling, or cooling only, or
heating only.
Thanks to a flexible fan control, the RDF3xx / RDF4xx can also be used in
universal applications, e.g. fan coil-based cooling and floor heating, or chilled
ceiling and electrical heater etc. See also section 4.8 "Fan control".
4.5

Additional features

The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3)
is used to change over from heating to cooling mode and vice-versa. When the
water temperature is above 28 °C (parameter P37), the controller changes over to
heating mode, and to cooling mode when below 16 °C (parameter P36). If the
water temperature is between the 2 changeover points immediately after power up,
the controller starts in heating mode.
The water temperature is acquired at 30-second intervals and the operating state is
updated accordingly.
M
16
28
M Operating mode
T
Water temperature
w
The QAH11.1 cable temperature sensor for automatic heating/cooling changeover
can be replaced by an external switch for manual, remote changeover:
X2
M
T °C
The sensor or switch can be connected to the input terminal of X2 (factory setting)
or X1 depending on the commissioning of inputs X1 and X2. See also section 4.9
"Multifunctional input".
The controller acquires the room temperature via built-in sensor, external room
temperature sensor (QAA32), or external return air temperature sensor (QAH11.1)
connected to multifunctional input X1 or X2.
Inputs X1 or X2 need to be commissioned accordingly. See section 4.9 "Multi-
functional input".
RDF300.../RDF340.../RDF400... Basic Documentation
4BFunctions
T
[°C]
w
Cooling mode
Heating mode
X2
T
M
QAH11.1
3076Z03
Contact open
heating mode
Contact closed
cooling mode
CE1P3076en
28 Aug 2008